Soft Starter and PKZM Coordination: Sizing SCPD, Overload and Bypass Together

Time:2026-11-30   Author:As Beam   Browse:

Motor Starting · Combined Protection

A soft starter is almost never installed alone. It sits behind a short-circuit protective device and in front of a motor that needs overload protection, and the three parts must be selected together. This guide covers the pairing of Eaton S811+, S801+ and DS7 soft starters with PKZM motor protective circuit breakers, and the coordination checks that decide whether the combination survives a fault.

Soft starters are bought for one reason: to reduce the mechanical and electrical stress of starting. That same reduction changes the duty of every device around them. The start current is lower but lasts longer; the thermal load on the motor is different; the short-circuit protective device must still clear a fault that the soft starter is bypassing at the time.

The result is that a soft starter selection cannot be finished without the protective devices, and the protective devices cannot be finished without knowing the starting profile. This article treats them as one selection.

The three devices and what each protects

DeviceProtectsSized by
Fuse or MCCB (SCPD)The soft starter's thyristors and the cableThe starter's published SCPD table, not the motor current
Soft starterControls voltage ramp; provides run/stop and often bypassMotor full-load current and start duty
PKZM / overload relayThe motor against overload and phase lossMotor full-load current, with the class set by start time

The first row is where most installations go wrong. The SCPD for a soft starter is specified by the starter manufacturer in a table indexed by starter rating, because the thyristor's I²t withstand — not the motor's current — sets the requirement. A fuse chosen for the motor will often be too large to protect the thyristors, and one chosen for the thyristors may be too small to carry the motor current without nuisance operation.

Read the soft starter's SCPD table first. It is the only document that knows both the thyristor withstand and the starter's internal wiring. Everything else follows from it.

Why soft starting changes the fuse requirement

A direct-on-line start draws 6–7 × FLC for a few seconds. A soft start draws perhaps 3–4 × FLC for longer — often 15–30 seconds for a high-inertia load. The heating effect on the fuse is the integral of current squared over time, so a longer, lower start can deposit as much energy as a shorter, higher one.

Starting methodTypical currentTypical durationFuse consideration
DOL6–7 × FLC2–8 sShort, high peak; aR or gG both viable
Soft start3–4 × FLC10–30 sLower peak but longer; check the I²t, not the peak
Star-delta2–3 × FLC5–15 sTransition spike can trip a marginal fuse
VFD1–1.5 × FLCContinuous rampaR only; gG will not protect the rectifier

For a soft starter the practical consequence is that a fuse sized exactly on FLC may operate during a long ramp, particularly in a hot enclosure. The manufacturer's SCPD table usually already accounts for this, which is another reason to use it rather than a calculation.

PKZM selection: the range must bracket the set point

A PKZM motor protective circuit breaker combines short-circuit protection (magnetic) with adjustable overload (thermal) in one device. The two functions use different references:

  • The thermal range must bracket the motor's full-load current with the setting in the middle of the range, not at its end. A setting at the top of the range leaves no margin for a hot day.
  • The magnetic trip must be above the starting current. For a soft start, the starting current is lower, so this is easier than for DOL — but a soft starter with a bypass contactor can produce a transient that trips a marginal magnetic setting.
  • The frame size must match the motor's current, not the contactor's. A 25 A frame cannot be set to 32 A.

PKZM0 covers the small motor range up to about 25 A, and the larger frames extend the range upward. The setting dial is calibrated for a 40 °C ambient; in a hotter panel the set point must be adjusted or the device derated.

Set the overload in the middle third of the range. A setting at either end has no adjustment left when the motor is replaced with a slightly different one, and it is the most common reason a PKZM is replaced rather than adjusted.

Coordination: type 1 and type 2

IEC 60947-4-1 defines two coordination levels between the SCPD and the starter:

TypeAfter a short circuitPractical meaning
Type 1Damage to the starter is acceptable; it may need replacementCheaper SCPD, higher downtime after a fault
Type 2No damage other than contact welding that can be cleanedFaster restart; requires a faster SCPD

The starter manufacturer publishes the fuse or breaker types that achieve each level. Specifying “Type 2” without using the listed device does not achieve it; the coordination is a tested combination, not a calculation.

Worked example: 55 kW pump, soft start

A 55 kW pump motor at 400 V draws about 100 A full load with a 25-second ramp. Direct-on-line would exceed the supply's starting current limit, so a soft starter is specified.

Step 1: starter rating. The starter must carry 100 A continuously and provide enough torque for the ramp. A unit rated for the next frame above 100 A is selected.

Step 2: SCPD. The starter's table for that frame lists specific fuse and breaker options for Type 1 and Type 2 coordination. Choosing Type 2 for a pump that must restart quickly selects a faster fuse, at a higher cost.

Step 3: overload. A PKZM sized to bracket 100 A, set at 100 A in the middle of its range, mounted adjacent to the starter.

Step 4: thermal. The starter dissipates heat during the ramp, the PKZM dissipates a little continuously, and the fuse dissipates continuously. In a sealed enclosure the three together often decide the enclosure size.

Step 5: the bypass contactor, if used, is rated for the motor current and switched after the ramp — its coil and auxiliary contacts follow the rules in the contactor article.

Common mistakes

  1. Sizing the SCPD on motor current. The starter's thyristor withstand, not the motor, sets the requirement.
  2. Setting the overload at the top of its range. No margin, and replacement motors rarely match exactly.
  3. Ignoring the internal heat of the starter. Soft starters dissipate during the ramp and the enclosure must be sized for it.
  4. Assuming a soft starter protects the motor. It controls voltage; overload protection is still a separate device.
  5. Using a slow SCPD and claiming Type 2. Type 2 requires the tested combination.

FAQ

Can a soft starter run without a bypass contactor?

Yes, but the thyristors then carry the full motor current continuously and dissipate more heat. Bypass is usual above a certain rating for thermal reasons.

Does a soft starter reduce the fuse rating?

It can reduce the starting current, but the SCPD requirement is set by the starter's own withstand. In many cases the fuse required is the same or larger than for DOL, not smaller.

Can I use a PKZM instead of a fuse plus relay?

Yes, and it saves panel space. It must be one of the types the starter manufacturer lists for the coordination level required.

What class overload for a 25-second ramp?

The class must cover the ramp without tripping. Class 10 covers most pump starts; longer ramps may need Class 20 or a higher class device.

Summary

Soft starter selection is a three-device problem. The SCPD follows the starter's table, the overload follows the motor's current with the setting in the middle of its range, and the starter itself follows the starting duty. The coordination level — Type 1 or Type 2 — decides which combination is acceptable, and it is a tested combination rather than a calculated one.

Get the order right: starter, then SCPD from its table, then overload, then thermal and mechanical. The reverse order — starting from the fuse you already stock — is how panels end up with a correctly rated fuse that does not protect the thyristors it is meant to protect.