Photovoltaic Protection · Fuse Selection Guide
A PV string fuse is not a general-purpose DC fuse with a solar label on it. It has to survive continuous reverse current, high ambient temperature inside a combiner box, and a fault current that is often less than twice the rated current. This guide works through the four Bussmann PV families — 10 × 38 mm ferrule, 14 × 65 mm ferrule, NH blade and the high-current XL styles — and shows which one fits which part of the array.
Photovoltaic protection has an unusual property: the available fault current is small. A string of crystalline modules produces a short-circuit current only about 1.1 to 1.25 times its maximum power current, because the modules themselves limit the current. A fuse therefore cannot rely on a large fault current to melt it quickly. It must open reliably at modest overloads, over years of thermal cycling, without nuisance operation on hot days.
That single fact explains most of the design rules that follow: the fuse rating must sit in a narrow band between the string's maximum power current and its short-circuit current, the ambient derating matters more than in any other application, and the standard the fuse is tested to (IEC 60269-6, UL 2579) is different from the one used for industrial DC fuses.
A grid-connected array has three protection zones, and they use different fuse types.
| Zone | Duty | Typical Bussmann family |
| String, per-pole in the combiner | Reverse-current protection of one string against the rest of the array | PV-A10 (10 × 38 mm), PV-A14LF (14 × 65 mm) |
| Combiner output / sub-array | Protection of the aggregated string current | PV-ANH (NH1 to NH3), PV-01XL / 2XL / 3L |
| Inverter DC input | Fault protection and isolation of the inverter DC bus | PV-2XL / 3L at 1500 V, or dedicated DC-link fuses |
The families are not interchangeable across zones, because the mechanical interfaces differ: a 10 × 38 mm ferrule fuse needs a modular holder on DIN rail, an NH blade fuse needs an NH base, and an XL fuse bolts to a busbar. Choosing the family is therefore a mechanical decision as much as an electrical one, and it is usually made first.
This is the string-level workhorse: 1 A to 20 A at 1000 V d.c., 50 kA breaking capacity, gPV and UL PV rated. It comes in three mechanical versions that share the same electrical data:
| Version | Mounting | Where it goes |
| PV-xA10F | Cylindrical ferrule, 10 × 38 mm | Modular fuse holder on DIN rail (CHPV or equivalent) |
| PV-xA10-T | Bolt fixing, 58.9 mm overall | Direct bolted connection to a busbar |
| PV-xA10-1P / -2P | PCB fixing, single or double ended | Soldered or clipped to a printed circuit board |
The electrical data are the same across versions, which is convenient: a design can move from a DIN-rail holder to a PCB without re-checking I²t. Representative values from the catalogue:
| Current | Pre-arcing I²t | Total I²t at 1000 V | Watts at 0.8 In / In |
| 1 A | 0.2 A²s | 0.4 A²s | 0.8 / 1.5 W |
| 5 A | 19 A²s | 50 A²s | 1.0 / 1.6 W |
| 10 A | 7 A²s | 70 A²s | 1.2 / 2.3 W |
| 15 A | 15 A²s | 160 A²s | 1.7 / 2.9 W |
| 20 A | 34 A²s | 350 A²s | 2.1 / 3.6 W |
Note the non-monotonic pre-arcing values: 8 A has a lower pre-arcing I²t (3 A²s) than 6 A (30 A²s). This is a real feature of the published table, caused by different element geometries at adjacent ratings, and it is why PV string fuses must be selected from the table rather than interpolated.
At 1300–1500 V d.c. the 10 × 38 mm body runs out of arc-quenching length, so the range moves to a 14 × 65 mm ferrule. Currents run from 2.25 A to 32 A, which covers most modern high-voltage string configurations. Three mounting variants exist: PV-xA14LF (cylindrical, for a modular holder), PV-xA14L-T (bolt fixing) and PV-xA14LF10F (cylindrical with 10 mm fixings, for a specific holder family).
The voltage annotation in this range needs care. The table splits into a 1500 V d.c. section up to 20 A and a 1300 V d.c. section at 25 A and 32 A. A 32 A link is therefore a 1300 V part, not a 1500 V part, and a 1500 V string at 30 A has no single-pole solution in this family.
From 32 A to 400 A the range switches to NH blade fuses in sizes NH1, NH2 and NH3, rated 1000 V d.c. (IEC and UL). These are the parts used at combiner outputs and in fused switch-disconnectors.
| Size | Current range | Example: current | Pre-arcing | Total at 1000 V | Watts |
| NH1 | 32 – 200 A | PV-100ANH1, 100 A | 1,300 A²s | 11,700 A²s | 8 / 16 W |
| NH2 | 160 – 300 A | PV-250ANH2, 250 A | 17,000 A²s | 136,000 A²s | 19 / 38 W |
| NH3 | 315 – 400 A | PV-400ANH3, 400 A | 61,000 A²s | 490,000 A²s | 32 W |
Each current rating is offered as a plain blade (PV-xxANH1), a version with bolt holes (-B) and, for some ratings, a version with bolt holes and a specific blade configuration (-BL). The electrical data are identical; the suffix describes the blade drilling, which must match the base. Ordering the wrong suffix produces a fuse that physically will not seat.
There is also a microswitch option (170H0236, 170H0238) that clips to the blade to give a remote indication when the fuse operates — relevant where the combiner is not accessible during operation.
Above 400 A, or where 1500 V is required at currents the NH range does not cover, the XL and 3L styles take over. These are bolted or bladed links in body sizes 01, 2 and 3, rated 1000 V or 1500 V d.c.
| Family | Size | Voltage | Current | Connection |
| PV-xA-01XL | 01 | 1000 V d.c. | 63 – 160 A | Bladed, 50 kA breaking |
| PV-xA-2XL | 2 | 1000 V d.c. | 160 – 355 A | Bladed |
| PV-xA-3L | 3 | 1000 V d.c. | 350 – 600 A | Bladed, 50 kA breaking |
| PVS-xA-3L-U-15 | 3 | 1500 V d.c. | 250 – 500 A | Bladed, 1500 V family |
The I²t spread in this group is large and matters. A 350 A / 3L part passes 161,200 A²s at 1000 V, while a 500 A / 3L at 1500 V passes 1,890,000 A²s — more than ten times as much. Inverter DC inputs protected by the larger parts therefore need a correspondingly robust upstream device.
Steps 2 and 3 usually leave only one or two permissible ratings. If they leave none, the array is misconfigured — for example too many parallel strings for the module's series fuse rating — and no fuse choice will fix it.
A combiner box in direct sun runs 20–30 °C above ambient air, and the fuse is usually the hottest component in it. PV fuses are specified with temperature derating curves that typically reduce usable current by about 0.5% per °C above 25 °C, but the exact curve is part-specific and should be read from the datasheet rather than assumed.
Two consequences. First, a 15 A fuse in a 70 °C combiner is not a 15 A fuse; it may be a 13 A fuse, which then sits too close to the string's Impp and operates on a hot afternoon. Second, replacing a failed fuse with the next size up “because it kept blowing” is the wrong response: the correct response is to check whether the failure was thermal (nuisance) or electrical (genuine fault), because upsizing may exceed the module's series fuse rating.
The holder is part of the protection chain and is often the weakest link mechanically. For the 10 × 38 mm range the CHPV family provides 1-pole and 2-pole modular holders on DIN rail, rated 1000 V d.c., 32 A (IEC) / 30 A (UL), 33 kA breaking, with an optional neon indicator. Terminal capacity is 1 to 25 mm² copper, which covers 4 mm² and 6 mm² string cable comfortably.
For NH blade fuses the base must match both the size (NH1/NH2/NH3) and the blade drilling. The catalogue lists bases with and without microswitch provision; where remote indication is required, the microswitch is a separate item fitted to the base or clipped to the blade, depending on the design.
For the bolted styles, the fixed-centre bases (170H3003 to 170H3006) cover 1000 V and 1400 V at 630 A and 1250 A with centre distances of 80 mm and 110 mm. These are the parts that convert a bolted square-body fuse into a serviceable item rather than a permanently bolted connection.
A PV fuse is not primarily there to clear a short circuit in its own string. It is there to protect a string against the other strings. When one string develops a fault — a shorted junction box, a damaged cable, a failed bypass diode — the healthy strings feed current backwards into it. That reverse current is the sum of the other strings' currents, and it can be several times the faulted string's own Isc.
This has three consequences that shape selection:
The module manufacturer's series fuse rating is the upper bound here: it defines the maximum reverse current the module can withstand without cell damage. A fuse above that value protects the cable but not the modules, and the modules are the more expensive item.
The two standards test different duties. A gG fuse is tested for cable protection: it must carry overload current for a defined time and then operate within a time-current band. A gPV fuse is tested for a duty where the current is limited by the source itself: it must operate reliably at currents only slightly above its rating, repeatedly, at high ambient, and it must not be damaged by continuous operation close to its rating.
In practice this shows up in the time-current curve. A gPV fuse has a tighter band at low overloads, because that is where PV faults live — the available fault current from a string is rarely more than 1.25 × Isc. A gG fuse with the same rating may sit above that band and never operate, or may operate too slowly to protect the module.
In a two-stage arrangement — string fuses in the combiner, then a larger fuse at the combiner output — the two must be selective. A fault in one string must operate the string fuse and nothing else.
The check is done on the time-current curves at the fault current level. The string fuse's total clearing time at the available reverse current must be shorter than the combiner fuse's pre-arcing time at the same current, with a margin. In most designs the ratio of ratings (typically 4:1 or more between string and combiner fuse) makes this comfortable, but it should be verified rather than assumed, particularly where strings are aggregated in several stages.
| Stage | Typical rating | Protects | Must not operate for |
| String fuse | 1.25 × Isc, capped by module series rating | String cable and modules under reverse current | Normal reverse current from shaded strings |
| Combiner fuse | Sum of string currents plus margin | Combiner output cable and switch-disconnector | Loss of one string (that is a string-fuse event) |
A module string has Isc 13.5 A at STC, Impp 12.8 A, and the module's series fuse rating is 25 A. The array maximum system voltage is 1500 V d.c., measured at −10 °C open circuit.
Step 1: minimum fuse rating is 1.25 × 13.5 = 16.9 A, so 20 A is the smallest permissible standard rating in the 10 × 38 mm family. Step 2: the module's series fuse rating caps the choice at 25 A. So the band is 20–25 A.
Step 3: voltage. The 10 × 38 mm PV-A10 range is rated 1000 V d.c., so it cannot be used on a 1500 V array regardless of current. The design must move to the 14 × 65 mm PV-A14LF family, where 20 A is rated 1500 V d.c. Step 4: the 20 A A14LF part has 34 A²s pre-arcing and 400 A²s total, with 3.8 W at In, which is acceptable in a ventilated combiner but should be checked against the enclosure temperature rise.
Step 5: holder. The 14 × 65 mm body needs a holder from that family, not the CHPV 10 × 38 mm holder. This is the step where projects most often discover a problem, because the combiner was designed around the smaller holder.
Notice that the current calculation was easy and the voltage and holder decisions were the ones that changed the design. That ordering — current, then voltage, then mechanics — is the reason the mechanical choice should never be made first.
A sub-array of 12 strings, each 15 A, aggregates to 180 A. After the combiner, a single fuse protects the output cable and the switch-disconnector. The design current is 180 A, and with a 1.25 margin the fuse is 225 A — but the next standard rating in the NH range is 250 A, and this part is PV-250ANH2: NH2 body, 17,000 A²s pre-arcing, 136,000 A²s total at 1000 V, 38 W.
Three checks follow. First, the NH2 base must be rated for 1000 V d.c. and for 250 A, which the standard NH2 range covers. Second, the 38 W loss inside the combiner adds to the string fuses' losses — twelve string fuses at roughly 2 W each is another 24 W — so the enclosure thermal calculation must include all of it. Third, the output cable's short-circuit withstand must exceed 136,000 A²s, which for a 95 mm² copper cable it does comfortably.
The interesting part of this example is that the string fuses and the combiner fuse are in the same enclosure but in different families: 10 × 38 mm ferrule for the strings, NH2 blade for the output. Two holders, two base types, two spare-part lines. That is normal, and it is why combiners are laid out early in the design, not at the end.
PV fuse failures are rarely mysterious, but they are frequently misdiagnosed because the fuse is replaced without checking why it operated.
| Symptom | Likely cause | What to check before replacing |
| One fuse per combiner, repeated over months | Thermal: rating too close to Impp in a hot enclosure | Enclosure temperature, derating curve, holder contact condition |
| Several fuses in the same string position | Genuine reverse-current fault or failing modules | String I-V curve, bypass diodes, cable insulation resistance |
| Fuse body discoloured, no element rupture | Overheating at the terminal, not a fuse fault | Terminal torque, contact surface, holder spring force |
| Fuse operates at dawn or in winter | Voltage-related, not current-related | Voc at low temperature versus fuse d.c. rating |
The fourth row is the one that gets missed. A fuse that operates in cold weather is being asked to break a voltage above its rating, and the fix is a higher-voltage family, not a larger current rating.
A PV fuse should carry both IEC 60269-6 (the PV-specific part of the IEC fuse standard) and a UL recognition under UL 2579 for the North American market. The marking on the body normally includes the rated voltage with the d.c. suffix, the current, the gPV class and the breaking capacity.
Two practical points. First, a fuse marked 1000 V d.c. is not rated for 1000 V a.c. or for a mixed waveform; the d.c. rating is derived from a specific test circuit with a specific time constant. Second, the breaking capacity figure matters less in PV than in industrial applications, because the array cannot deliver a large fault current — but the voltage rating matters more, because the array can deliver full open-circuit voltage indefinitely.
Can I use an industrial DC fuse instead of a gPV fuse?
Only if it carries a published PV rating. IEC 60269-6 and UL 2579 test for the specific duty of a PV string — continuous operation near Isc at high ambient — which a general DC fuse is not tested for.
Why does the 10 × 38 mm range stop at 20 A?
Body volume. Above roughly 20 A the element needs more arc-quenching material than a 10 × 38 mm body provides at 1000 V, so the range moves to 14 × 65 mm and then to NH.
Do I need a fuse on both poles?
On an unearthed PV array both conductors carry fault current in some fault scenarios, so both are protected. On a functionally earthed system the requirement differs and the local standard governs.
What does the -15 suffix mean?
It identifies the 1500 V variant of a family that is otherwise 1000 V. The electrical data differ, not just the marking.
Is a higher breaking capacity always better?
It is not a substitute for correct current selection. A 50 kA fuse that is rated too close to Impp will still operate thermally; breaking capacity only matters at the fault current the array can actually deliver, which for a PV array is modest.
PV fuse selection is constrained at both ends: the fuse must be large enough not to operate at Isc in a hot combiner, and small enough not to exceed the module's series fuse rating. The voltage rating must cover Voc at the coldest expected temperature, and the mechanical family follows from where the fuse sits — ferrule in a modular holder, NH blade in a base, XL bolted to a busbar.
Get the family right first. Within a family the electrical variants share data, which makes late changes cheap; across families nothing is shared, and a late change means a new holder, a new base and a new panel layout.