Motor Control · Contactor Selection
A contactor is ordered by three numbers that are rarely on the same page: the AC-3 current at the utilisation voltage, the coil voltage and frequency, and the auxiliary contact configuration. Get any one wrong and the contactor either chatters, drops out under voltage dip, or arrives with no contacts to wire the interlock. This guide covers the Eaton DILM, DILH and XT families and the accessories that are usually ordered separately.
Contactor selection looks simple until the first commissioning. The contactor pulls in, the motor runs, and then the coil buzzes at 50 Hz on a 60 Hz supply, or it holds at 85% voltage but drops out at 80% when a large motor starts elsewhere on the board, or the interlock cannot be wired because the auxiliary block was not ordered.
Each of those is a specification gap, not a product fault. This article sets out the four parts of a complete contactor specification and the ones most often left out.
A contactor carries several current ratings simultaneously, and they are not interchangeable:
| Rating | What it describes | When it governs |
| AC-1 | Non-inductive or slightly inductive load | Resistive heating, lighting |
| AC-3 | Squirrel-cage motor, breaking at rated current | Motor circuits — the usual basis |
| AC-4 | Motor with inching, plugging, frequent operation | Hoists, cranes, high-duty cycling |
| DC-1 / DC-3 / DC-5 | DC loads of increasing inductance | DC coils, DC motors, electromagnetic loads |
For DILM contactors the model number generally corresponds to the AC-3 rating at 400 V in the smaller frames — DILM7 is 7 A, DILM12 is 12 A, DILM25 is 25 A, DILM38 is 38 A — and the correspondence continues through the larger frames at their named currents (DILM50, DILM65, DILM95, DILM150 and so on). The rating is not an absolute: the same frame carries a different AC-3 current at 690 V than at 400 V, and the catalogue table must be read at the actual utilisation voltage.
A coil has a pick-up voltage and a drop-out voltage, both expressed as a percentage of nominal. Typical values are pick-up at 85% and drop-out at between 20% and 75% depending on the design. The consequence is that the coil's nominal voltage must match the control circuit's actual voltage, not its nominal one.
| Situation | Effect on the coil | Correct action |
| 400 V nominal coil on a 415 V supply | Within tolerance (about 104%) | Acceptable; use the wide-range coil where offered |
| 230 V coil on a 240 V supply | About 104%, acceptable but hot | Prefer a 220–240 V wide-range coil |
| 50 Hz coil on a 60 Hz supply | Impedance rises, coil current falls, may not pick up | Order a 50/60 Hz coil |
| Long control cable | Voltage drop at pick-up; coil may chatter | Check drop; consider a DC coil |
The fourth row is the one that produces intermittent faults. A 230 V AC coil drawing 10 VA through 500 m of 1.5 mm² cable drops several volts at the instant of pick-up, and the contactor chatters rather than closing. A DC coil avoids the inrush problem entirely and is increasingly the default in modern panels.
An auxiliary contact block is usually a separate item. A complete specification states how many normally-open and normally-closed contacts are needed and whether they are front-mounted, side-mounted, or integrated.
The practical advice is to count the auxiliary contacts on the schematic before ordering, not after. Retrofitting a side-mounted block to an installed contactor is possible but often blocked by adjacent components.
| Accessory | Purpose | Consequence if omitted |
| RC suppressor / varistor | Limits the inductive kick when the coil de-energises | PLC output damage, arcing at the control contact, EMI |
| Surge suppressor module | Protects the coil against supply transients | Coil failure after a lightning event or capacitor switching |
| Mechanical interlock | Prevents two contactors closing together | Phase-to-phase short on reversing or star-delta changeover |
| Terminal shroud | Finger-safe protection at the terminals | IP20 not achieved; touch protection fails |
| Mounting adapter | Allows direct mounting of the overload relay | Wiring between contactor and relay is longer and less reliable |
The first row is the most consequential. A coil without a suppressor generates a transient of several hundred volts when it opens, and the control relay or PLC output that drove it takes the stress. In panels with many contactors the failure rate of control outputs tracks the presence or absence of suppressors almost directly.
Choose the suppressor type deliberately: an RC network suppresses the transient but adds a small leakage current that can hold a sensitive relay; a varistor clamps harder but has a finite life; a diode is only for DC coils and slows drop-out.
The three families overlap and are frequently confused.
| Family | Character | Typical use |
| DILM | Standard AC-3 motor contactor, wide frame range | General motor control, the default choice |
| DILH | Higher rating in a given frame, often for DC and special duty | Heavy duty, DC switching, where DILM runs out of rating |
| XT | Compact frame, high AC-3 rating per size, screw or spring terminals | Space-constrained panels, new designs |
A practical rule for retrofits: match the frame and the mounting pattern first, then the rating. A contactor of the right rating but a different frame will not fit the existing DIN rail arrangement or accept the existing overload relay.
A 30 kW four-pole motor at 400 V draws about 56 A AC-3. The contactor must be rated at least 56 A AC-3 at 400 V, which points to the DILM65 frame. The overload relay is selected on the same current with an adjustable range that brackets 56 A.
The coil is 230 V AC 50/60 Hz in a panel fed from a 230 V control transformer. Auxiliary contacts required: one NO for the seal-in, one NC for the PLC feedback — two contacts, so a contactor with at least one NO and one NC fitted plus space for a side block, or a two-contact front block.
Accessories: RC suppressor across the coil (driven by a PLC output), terminal shroud for IP20, and a mechanical interlock only if the application is reversing. The complete specification has eight lines; a typical purchase order has two.
Can I use an AC contactor on DC?
Only at greatly reduced current, and only with a DC-rated contactor. The arc extinguishing principle differs; an AC contactor on DC may not break the arc at all.
Why does my contactor hum?
Usually a shading ring or pole face issue, or a coil voltage/frequency mismatch. A 50 Hz coil on 60 Hz will hum and may not seal.
Do I need a suppressor on every coil?
Wherever the coil is switched by a semiconductor output, yes. Where it is switched by a mechanical contact, it is still good practice.
Is a larger contactor always safer?
No. A larger contactor has a higher drop-out current and may not hold under voltage dip; it also costs panel space and money without improving the duty.
A complete contactor specification has four parts: AC-3 current at the utilisation voltage, coil voltage with frequency and tolerance, auxiliary contact count and type, and accessories including the suppressor and interlock. The first two decide whether it works; the last two decide whether it keeps working.
The most common gap is the auxiliary contact count, followed by the suppressor. Both are cheap, both are ordered separately, and both are discovered late — usually during commissioning, when the panel is closed and the wiring is complete.