Bussmann 170M Voltage Classes: 690 V, 1000 V and 1250 V Selection Across Sizes 00 to 3

Time:2026-11-19   Author:As Beam   Browse:

Semiconductor Protection · Fuse Selection Guide

A 400 A Bussmann 170M fuse exists in three voltage classes — 690 V, 1000 V and 1250 V — and they are not interchangeable mechanically or thermally. The 690 V version fits size 00; the 1000 V version needs size 1*; the 1250 V version is a different body again, with roughly three times the let-through I²t. This guide explains what the voltage class changes, how to read the catalogue numbers behind it, and how to pick the right class, size and I²t for a real installation.

Anyone who has ordered a square-body fuse from a catalogue has met this problem. The system needs 400 A. Search the 170M tables and three candidates appear: 170M2621 at 690 V, 170M3975 at 1000 V, 170M3148 at 1250 V. All three are rated 400 A, all three are aR high-speed links to IEC 60269-4, and all three look like the same grey block in a photograph. They are not the same product. They differ in body size, in pre-arcing and clearing I²t, in watts loss, and in the mechanical envelope they occupy inside the enclosure.

The reason is not commercial. A fuse does not interrupt current by melting a wire — it interrupts by forcing the arc voltage above the system voltage until the current falls to zero. That arc voltage is generated inside the body, and a longer body produces a higher arc voltage. Voltage class is therefore a physical property of the fuse, not a label on it. Everything else — size, I²t, losses — follows from that.

What the voltage class actually changes

In an aR semiconductor fuse the element is a punched silver strip, sometimes with a tin or M-effect overlay, wound inside a ceramic body filled with quartz sand. On a fault the element vaporises, the sand fuses into glass (fulgurite), and the arc burns in a narrow channel. The voltage across that channel is roughly proportional to its length. To hold off 1000 V instead of 690 V, the manufacturer must give the arc a longer path.

Practical consequences, all visible in the catalogue tables:

  • Longer body, larger size. The 400 A / 690 V link fits size 00 (about 79 mm tall). The 400 A / 1000 V link needs size 1*, and the 1250 V link also uses size 1* but with a different element geometry.
  • More silver, more I²t. A longer element with more mass takes more energy to vaporise, so both pre-arcing and clearing I²t rise. At 400 A the pre-arcing value goes from 18,000 A²s at 690 V to 42,000 A²s at 1000 V and 53,000 A²s at 1250 V.
  • More watts. Resistance per unit length is set by the element cross-section, but the longer element plus the larger terminal structure adds loss. At 400 A, losses are 70 W, 75 W and 70 W respectively — the 1250 V part is thermally efficient because its element is wider, not longer, than the 1000 V part.
  • Higher minimum current. The 690 V range starts at 10 A in size 000; the 1000 V range starts at 20 A. Small currents are harder to interrupt at high voltage because the arc is weak relative to the recovery voltage.
The rule that follows from this: voltage class is chosen by the system voltage, never by convenience. You may always use a fuse with a higher voltage rating than the system needs — a 1250 V link on a 690 V busbar is electrically valid — but you cannot use a lower one, and you must then accept the larger size, higher I²t and different thermal behaviour that come with it.

The three classes in numbers

The 170M range covers three IEC voltage classes. The current ceilings below are taken from the published catalogue tables and show how the same body size holds less current as the voltage rises.

Voltage classSizes availableCurrent rangeTypical use
690 V a.c. (IEC) / 700 V a.c. (UL)000, 00, 1*, 1, 2, 310 A to 2000 ADrives, rectifiers, general industrial DC links
1000 V a.c. (IEC and UL)00, 1*, 1, 2, 320 A to 1400 A1000 V drives, wind converters, marine DC
1250 V a.c. (IEC) / 1300 V a.c. (UL)1*, 1, 2, 350 A to 1400 AMining drives, traction auxiliaries, 1250 V networks

Note the asymmetry at the top of the range. At 690 V a size 3 body carries 2000 A; at 1000 V the same size stops at 1400 A. The body did not shrink — the element did, because a longer arc channel consumes more of the available internal volume. This is why substitution in the other direction (fitting a 1250 V link where a 690 V link was specified) so often fails on current: the higher-voltage part you need may simply not exist at the current you need.

Size ladder: what fits what

Body size is the second decision, and it is driven by two constraints that pull in opposite directions — current capacity and available space. The table below gives the published current window for each size in each class.

Size690 V range1000 V range1250 V range
00010 – 315 Anot offerednot offered
0025 – 400 A20 – 315 Anot offered
1*40 – 630 A50 – 400 A50 – 400 A
1200 – 900 A160 – 630 A160 – 630 A
2400 – 1250 A250 – 800 A250 – 1000 A
3500 – 2000 A315 – 1400 A315 – 1400 A

The overlap between adjacent sizes is deliberate: at 400 A you can choose size 00, 1* or 1 in the 690 V class. The choice is then settled by I²t, by watts loss, and by what the fuseholder or busbar arrangement will accept.

Same current, three classes: the I²t penalty

This is the table that decides most real designs. The same nominal current produces very different let-through energy depending on the voltage class, because the element mass changes.

Current690 V partPre-arcing / clearing1000 V partPre-arcing / clearing1250 V partPre-arcing / clearing
100 A170M1317 (00)695 / 4,650 A²s170M4810 (00)950 / 6,850 A²s170M3141 (1*)750 / 5,950 A²s
200 A170M1320 (00)4,200 / 28,000 A²s170M4813 (00)5,600 / 40,500 A²s170M3144 (1*)5,150 / 41,000 A²s
400 A170M2621 (00)18,000 / 125,000 A²s170M3975 (1*)42,000 / 250,000 A²s170M3148 (1*)53,000 / 335,000 A²s
630 A170M3023 (1*)48,500 / 325,000 A²s170M4974 (1)125,000 / 755,000 A²s170M4147 (1)130,000 / 660,000 A²s

At 400 A the 1250 V link passes nearly three times the pre-arcing energy of the 690 V link. That difference is not academic: the semiconductor you are protecting has an I²t withstand curve, and the fuse must stay below it with margin across the whole fault-current range. If the drive was designed around a 690 V fuse and someone substitutes the 1250 V part because it was in stock, the protected device may now be outside its own let-through envelope.

Two nuances worth noting. First, pre-arcing I²t scales faster than clearing I²t here, because clearing energy includes the arc period, which is dominated by system voltage and fault level rather than element mass. Second, the 1250 V / 100 A part has lower I²t than the 1000 V / 100 A part — element design is not monotonic with voltage. This is why the catalogue must be read per part number, never interpolated across classes.

The one-way substitution rule

Higher voltage rating on a lower-voltage system is permitted. The fuse will interrupt the fault; it will simply be larger and slower in I²t terms. The reverse is never permitted, and there is no derating that makes it safe: the 690 V element physically cannot generate enough arc voltage to clear a 1000 V fault. It will rupture, and it may do so in a way that leaves the enclosure live.

System voltageAcceptable fuse classesConsequence
400 – 690 V690 V, 1000 V, 1250 VHigher classes cost size, I²t and watts
691 – 1000 V1000 V, 1250 V690 V part must not be used, even at reduced current
1001 – 1250 V1250 V onlyNo substitute exists in this family above 1250 V

There is one legitimate use for the one-way rule: standardising a plant on a single class. A site running 690 V and 1000 V sections can stock only 1000 V links, accepting the larger body and higher I²t in the 690 V sections in exchange for one spare-parts list. That is a maintenance decision, and it should be written down and reflected in the I²t calculation, not discovered during a retrofit.

Five-step selection procedure

The sequence below is the one that avoids rework. Electrical sizing comes before mechanical sizing, because the electrical answer constrains the size, never the other way round.

  1. Fix the voltage class from the highest sustained system voltage, not the nominal. A 690 V drive on a 690 V supply with regeneration can see higher; use the converter's published DC-link and output ratings.
  2. Calculate the continuous current the fuse will carry, then apply the enclosure and altitude factors. For semiconductor fuses the usual starting point is 1.0 × the RMS device current with a thermal margin, then verify against the derating curves rather than assuming a fixed 1.25.
  3. Check I²t against the protected device at the prospective fault current, using the clearing value, and keep margin for ageing and for the asymmetry of the first half-cycle.
  4. Check watts loss against the enclosure's thermal budget. Losses are published per part at rated current; at partial load they fall roughly with the square of the current ratio.
  5. Confirm the mechanical envelope — body size, centre distance, blade or bolted tag arrangement — against the fuseholder or busbar you intend to use.
Do step 3 before step 5. If you size the fuseholder first, you will end up choosing a fuse that fits the holder rather than one that protects the semiconductor — and the difference at 400 A is a factor of three in let-through energy.

Three worked examples

Example 1 — 690 V drive, 400 A continuous, existing size 00 holder

A rectifier front-end draws 400 A RMS at 690 V. The existing holder takes size 00. The 690 V size 00 part at 400 A is 170M2621: pre-arcing 18,000 A²s, clearing 125,000 A²s, 70 W. Checking the device's I²t withstand at the prospective fault current confirms it sits inside the clearing value with margin. Nothing changes.

Now suppose the site standardises on 1000 V links. The 1000 V / 400 A part is 170M3975, size 1*. It will not fit the size 00 holder, and its clearing I²t is 250,000 A²s — double. Both the holder and the I²t check must be redone. This is the single most common retrofit error in 690 V systems.

Example 2 — 1000 V wind converter, 630 A, space constrained

A converter output stage runs 630 A at 1000 V. In the 1000 V class, 630 A is available in size 1 (170M4974: 125,000 / 755,000 A²s, 98 W). Size 00 stops at 315 A and size 1* at 400 A, so there is no smaller option — the current forces size 1 regardless of panel space. If the enclosure cannot take size 1, the design must change elsewhere: parallel paths, a different fuse family, or a mechanical redesign.

Example 3 — 1250 V auxiliary circuit, 100 A

At 1250 V the smallest size is 1*, so a 100 A circuit still occupies a size 1* body. The part is 170M3141: 750 / 5,950 A²s, 30 W. Notice that its I²t is close to the 690 V part rather than the 1000 V part — the 1250 V element at low current is not simply a scaled-up 1000 V element. Anyone comparing by voltage class alone would predict the wrong number here.

Watts loss and the enclosure

Losses matter more than they look. A single 630 A link at 98 W is not a problem in a ventilated cabinet, but six of them in a sealed 600 mm enclosure is 588 W of continuous heat, and the fuse is usually the item nearest the components that cannot take it. The published watts figure is at rated current; at 80% current the loss falls to roughly 64% of the published value, and at 50% to about 25%.

Two practical points. First, the watts figure is per fuse, so multiply by the number of poles. Second, the same current in a higher voltage class usually costs more watts — 400 A is 70 W at 690 V and 75 W at 1000 V — so a voltage-class upgrade quietly adds to the thermal budget even when the current rating looks unchanged.

Mechanical fit: what to measure

Once the electrical choice is fixed, measure five things before ordering. The dimension drawings published for each catalogue number give all of them, and they differ between sizes in ways that photographs do not show.

MeasurementWhy it decides the part
Body height and widthDetermines whether the fuse clears the enclosure door and adjacent busbars
Centre distance between tagsMust match the fuseholder; a 1* and a 1 body are not interchangeable even at the same current
Tag or blade thicknessSets the clamp force and therefore the contact temperature
Overall height including tagsUsually 15–25 mm more than the body alone; the value that catches people
Clearance to earthed metalSet by system voltage, not by fuse size

To give a concrete reference: a size 000/00 DIN 43653 link has a body height of 79.0 ± 1.0 mm, an overall height of at most 96 mm including the tags, and a body width of 36.3 mm. The next size up is roughly 25 mm taller and 10 mm wider — a difference that decides whether two rows of fuses fit in a 300 mm deep panel.

Five mistakes that recur

  1. Choosing by ampere rating alone. Three parts share the number 400 A and differ by a factor of three in I²t.
  2. Substituting a higher-voltage part without re-checking I²t. The substitution is legal electrically and illegal for the protected device if the I²t margin disappears.
  3. Ignoring the size step. Retrofitting 690 V to 1000 V at the same current usually moves the part up one body size, which breaks the holder and often the panel layout.
  4. Using AC current ratings on DC. The 1000 V figures in this range are a.c. ratings. A DC application needs a part with a published d.c. rating at the actual system voltage — several 170M variants carry separate 800 V or 1500 V d.c. ratings, and those are different catalogue numbers.
  5. Sizing on nominal current without derating. Enclosed, high-ambient or high-altitude installations change the usable current long before they change the voltage rating.

Reading a catalogue row correctly

Each row in a 170M table carries five numbers before the catalogue numbers, and misreading one of them is the usual source of a wrong part. The columns are: rated current, pre-arcing I²t, clearing I²t at the stated voltage, watts loss at 0.8 × In, and watts loss at In. In the 1250 V tables there is an additional clearing column, because the same element is characterised at both 1000 V and 1250 V, and the higher-voltage clearing value is the one to use for a 1250 V system.

Three details that catch people:

  • Two watts columns. The lower figure applies at 80% load. For thermal calculations at continuous rated current, use the higher one.
  • N/A entries. A missing catalogue number in a column means that combination is not produced — usually the indicator variant at a low current. It is not a discontinued part and it cannot be ordered.
  • Indicator variants. Suffixes such as -/80, -TN/80, -KN/110 or -FU/115 describe the microswitch fitted for remote indication. The electrical data above them are identical; the suffix changes the auxiliary contact, not the fuse.

This last point matters commercially. Two catalogue numbers that differ only by indicator suffix are the same fuse electrically, so a customer who needs the plain version should not be quoted the indicator version “because it was in the table first”.

Three mounting standards behind the same number

A 170M link at a given voltage and current is offered in several mechanical styles, and they are not interchangeable even when the electrical data are identical. The three that matter in IEC equipment are:

StyleStandardConnectionWhere it is used
DIN 43653IEC square body, bolted tagsBolted through tags, fixed centre basesEuropean drives, rectifiers, general industry
DIN 43620Blade type, NH patternBlades into a base, tool-free replacementDistribution, PV combiners, fused switches
US styleNorth American blade patternBlades, different thickness and spacingEquipment built to UL practice

All three appear in the 170M range at 690 V and 1000 V. The electrical tables are laid out separately for each, which is why the same current can appear three or four times in the catalogue with different body sizes and different I²t. A specification that says only “170M, 400 A, 690 V” is therefore incomplete: it does not identify the mechanical style, and the three styles have different centre distances.

Coordination with contactors and breakers

An aR fuse protects the semiconductor; something else protects the cable and provides isolation. The two duties must be coordinated, and the coordination is done at the fault-current level, not at the rated current.

The usual arrangement in a drive is aR fuse plus contactor plus thermal overload, or aR fuse plus a moulded-case breaker. The fuse must clear a semiconductor fault before the contactor's contacts weld, and the breaker must not trip on the fuse's normal load current. In practice this means checking the fuse's total clearing I²t against the contactor's withstand I²t at the prospective fault current, and checking that the breaker's instantaneous pickup sits above the fuse's pre-arcing curve at the same current.

Two rules that avoid most problems. First, never use a gG fuse where an aR is specified: the gG element is slower by design and will not protect the junction. Second, do not assume that a larger fuse improves coordination — a larger aR fuse passes more I²t, which can push the contactor outside its withstand.

Derating in practice

The published current rating assumes a defined set of conditions: free air, 20 °C ambient, single fuse, no enclosure. Real installations differ on all four counts, and the correction usually costs more current than the voltage-class decision costs I²t.

ConditionEffect on usable currentHow to handle it
Enclosure, no ventilationTypically 10–20% reductionUse the manufacturer's enclosure curve, not a rule of thumb
Ambient above 40 °CFalls roughly 1% per °C above 40 °CDerate, or improve airflow; do not upsize the fuse blindly
Fuses mounted side by sideEach fuse heats its neighbourKeep the published spacing; if not possible, derate further
Altitude above 2000 mReduced cooling and reduced insulation marginApply the altitude correction to both current and voltage

Altitude deserves a note in the 1000 V and 1250 V classes specifically. The voltage rating assumes a defined air clearance and pollution degree; above 2000 m the dielectric strength of air falls, and a part rated for 1000 V at sea level is not automatically rated for 1000 V at 3000 m. The catalogue derating table for the family applies — it is not a matter of judgement.

Ordering checklist

Before the part number is written into a BOM, six items should be settled. Each one has caused a re-order at some point.

ItemSettled by
Voltage classMaximum sustained system voltage, including regeneration
Current ratingRMS device current plus enclosure and ambient derating
I²t checkClearing I²t at the prospective fault current versus device withstand
Body sizeForced by the current window of the class, then by the holder
Mechanical styleDIN 43653, DIN 43620 or US, matching the existing base
Indicator variantWhether remote indication is wired; changes the suffix only

FAQ

Can I use a 1250 V fuse on a 690 V system?

Yes, provided the current rating exists in that class and you accept the larger body and higher I²t. It is common practice where a plant wants one spare part across mixed voltages.

Can I use a 690 V fuse at 1000 V if I reduce the current?

No. Derating current does not increase arc voltage capability. The fuse will fail to clear a 1000 V fault regardless of load.

Why does the same current have different I²t in different voltage classes?

Because the element mass differs. A longer arc channel needs a longer element, and a longer element takes more energy to vaporise. The clearing value also includes the arc period, which is longer at higher voltage.

Does a higher voltage class always mean more watts loss?

Usually, but not monotonically. At 400 A the 1000 V part is 75 W and the 1250 V part 70 W, because the 1250 V element is wider rather than merely longer. Always read the published value for the exact part.

How do I know which class a part belongs to from its number?

You cannot. 170M3023, 170M4974 and 170M4147 are all 630 A parts in different classes and the numbering does not encode the voltage class. Look the part up in the catalogue table, or read the voltage column of the datasheet.

What about DC applications?

A separate consideration. Several 170M variants carry d.c. ratings (for example 800 V d.c. or 1500 V d.c. sections), and the DC rating is specific to that variant. Never treat an a.c. voltage figure as a d.c. rating.

Summary

The 170M range is not one product line with optional voltage ratings. It is three mechanical families that share a naming convention. Voltage class sets the body length, the body length sets the element mass, and the element mass sets the I²t, the watts and the size step. Choose the class from the system voltage, choose the size from the current and the I²t, then confirm the mechanical envelope against the actual dimension drawing.

Get that order right and the catalogue becomes a lookup. Get it wrong and you will find out during commissioning, when a size 00 holder will not accept a size 1* fuse that the I²t calculation demanded in the first place.

New industry Technology regarding to Bussmann fuse, ABB breakers, Amphenol connectors, HPS transformers, etc. 