British Standard Fuses · Selection Matrix
Thirteen Bussmann BS88 series share one mounting standard and one set of body sizes, yet they are not interchangeable: voltage class, breaking capacity, element design and DC rating all differ. This guide maps all thirteen — LCT, LET, LMT, LMMT, CT, ET, FE, EET, FEE, FM, FMM, MT and MMT — against current range, voltage and duty, so the right series is chosen before the part number.
Anyone who has opened a British panel has met the BS88 fuse: a white ceramic body with offset bolted tags, held between two studs, and a catalogue that lists more variants for the same current than any other family in the Bussmann range. At 100 A, for example, the range offers ET, FE, FEE, LMT, MT and MMT parts, all fitting similar holders, all rated differently.
The reason is history. BS88 grew out of British industrial practice, where the fuse had to serve motor circuits, distribution boards and DC battery systems with one mechanical format. The format was standardised; the electrical duties were not. Understanding the resulting matrix is the difference between a correct selection and a fuse that operates on every motor start.
BS88 standardises the mechanical envelope: body diameter, overall length, tag offset, tag hole diameter and centre distance. It does not standardise the electrical characteristic, which is why the standard has parts:
A fuse marked to one part cannot be assumed to meet another. A Part 6 motor fuse in a distribution position will not protect the cable properly; a Part 2 fuse in a motor circuit will operate on starting current. Both fit the same holder.
The table below lists all thirteen series with their published voltage class and the current range actually available in each. It is the matrix that should be consulted first.
| Series | Voltage | Current range | Typical duty |
| LCT | 240 V a.c. / 150 V d.c. (IEC) | 6 – 20 A | Small distribution, control circuits |
| LET | 280 V a.c. / 150 V d.c. (UL) | 25 – 180 A | Distribution, higher breaking capacity |
| LMT | 240 V a.c. | 160 – 450 A | Heavy distribution, large cable |
| LMMT | 240 V a.c. | 400 – 900 A | Sub-main protection |
| CT | 690 V a.c. / 500 V d.c. (IEC) | 6 – 20 A | High breaking capacity, 90 kA RMS sym |
| ET | 690 V a.c. / 500 V d.c. (IEC) | 25 – 80 A | General industrial at 690 V |
| FE | 690 V a.c. / 500 V d.c. (IEC) | 35 – 100 A | Distribution at 690 V |
| EET | 690 V a.c. / 500 V d.c. (IEC) | 90 – 160 A | Distribution at 690 V |
| FEE | 690 V a.c. / 500 V d.c. (IEC) | 100 – 200 A | Distribution at 690 V |
| FM | 690 V a.c. / 450 V d.c. (IEC) | 180 – 350 A | Motor circuits, high current |
| FMM | 690 V a.c. / 450 V d.c. (IEC) | 400 – 700 A | Motor circuits, very high current |
| MT | 690 V a.c. / 350 V d.c. (IEC) | 160 – 355 A | Motor protection with DC rating |
| MMT | 690 V a.c. / 350–450 V d.c. | 180 – 710 A | Motor protection, largest body |
Two patterns stand out. First, the current ranges overlap heavily: between 160 A and 200 A there are six different series available. Second, the DC rating is not uniform — 150 V for the LCT/LET pair, 350 V for MT/MMT, 450 V for FM/FMM, 500 V for the CT/ET/FE group. That spread matters more than it looks, and it is where most DC misapplications originate.
Three variables generate the matrix: voltage class, breaking capacity and element characteristic. Each series is a fixed combination, and the manufacturer does not offer every combination in every size.
| Variable | Options within BS88 | Effect on selection |
| Voltage | 240 V, 280 V, 690 V a.c.; 150 to 500 V d.c. | Sets the minimum series; a 690 V system cannot use a 240 V part |
| Breaking capacity | From 40 kA d.c. up to 90 kA RMS symmetrical (CT) | Set by prospective fault current at the installation point |
| Characteristic | gG distribution, motor-rated (Part 6), fast (Part 4) | Determines whether the fuse tolerates starting current |
The practical consequence is that a specification of “BS88, 100 A, 690 V” is still ambiguous: it could be FE, FEE, EET or one of the motor-rated series at that current. The distinguishing question is not electrical at all — it is what the fuse is protecting.
A motor starting direct-on-line draws five to seven times its rated current for several seconds. A gG distribution fuse at the motor's rated current will operate during that start. The motor-rated series (FM, FMM, MT, MMT) use an element with a delayed characteristic that tolerates the start while still protecting the cable.
Selecting a motor fuse therefore starts from the motor's full-load current, not from the cable ampacity:
Step 3 is where a multiplier is often used instead of the curve, and it is the step that fails. A “1.75 × FLC” rule works for many small motors and fails for high-inertia loads with long acceleration, where the fuse must be larger or the starting method changed.
BS88 fuses carry DC ratings, and they differ sharply between series. This is the area where a plausible-looking substitution produces a fuse that cannot clear a DC fault.
| Series group | DC rating | Suitable for |
| LCT, LET | 150 V d.c. | 24/48/110 V battery systems, control supplies |
| MT, MMT | 350 V d.c. | Telecom and UPS battery strings up to 350 V |
| FM, FMM | 450 V d.c. | Higher-voltage battery and DC link circuits |
| CT, ET, FE, EET, FEE | 500 V d.c. | DC distribution up to 500 V, rectifier outputs |
None of these is a 1000 V DC fuse. A BS88 part in a modern 800 V or 1000 V battery system is outside its DC rating no matter which series is chosen — that application belongs to the square-body DC families, not to BS88. The distinction is easy to miss because the a.c. rating (690 V) looks higher than the DC system voltage.
A 45 kW four-pole motor at 415 V draws about 80 A full load, with a direct-on-line starting current around 480 A for six seconds. The fault level at the motor terminals is 25 kA.
Step 1: duty is motor starting, so a motor-rated series is required — not gG. Step 2: 415 V is within the 690 V class, so the ET or MT series are candidates by voltage. Step 3: at 80 A the available motor-rated parts include ET and MT; the choice depends on acceleration time. A six-second start at 6 × FLC rules out the smallest sizes and points to a rating around 100 A in the motor series, which in this range is FE or MT.
Step 4: cable. A 35 mm² cable at 100 A is protected comfortably. Step 5: breaking capacity. The 25 kA fault level is well within the 690 V series, which are rated far above that.
The interesting part is step 3: the same 80 A motor could be protected by three different series, and the decision comes from the acceleration time, not from the current. That is why the time-current curve, not the ampere rating, settles motor applications.
A substation battery at 110 V DC, 60 A continuous, with a prospective short-circuit current of 8 kA. The existing panel uses BS88 fuses in a bolted holder.
Step 1: 110 V DC is within the 150 V d.c. rating of LCT and LET, so those series are candidates. Step 2: at 60 A, LCT stops at 20 A, so LET is the series — its range runs to 180 A. Step 3: breaking capacity — 8 kA is modest and the LET series covers it. Step 4: the holder is the same bolted pattern, so the replacement is mechanically straightforward.
Now suppose the battery is upgraded to 220 V DC. LET's 150 V d.c. rating is exceeded, and the correct move is to a series with a higher DC rating — MT or MMT at 350 V d.c. — which changes the body size and therefore the holder. The electrical current is unchanged at 60 A; the mechanical envelope is not.
BS88 bodies come in the familiar lettered sizes (A1 through A4 in the British convention), and the size follows the current rather than the voltage. Practical implications:
That last point is the essential difference between the two families and worth stating plainly: in BS88, voltage class does not change the body size; in the 170M square-body range it does. Engineers who work with both regularly apply the wrong intuition in one direction or the other.
The difference between a distribution fuse and a motor fuse is a factor of roughly two in operating time at the same multiple of rated current. It is worth seeing the shape of the difference rather than the rule.
| Multiple of rating | Distribution (Part 2) behaviour | Motor (Part 6) behaviour |
| 1.5 × In | Operates within minutes | Does not operate (below the minimum operating current) |
| 3 × In | Operates in seconds | Operates in tens of seconds |
| 6 × In | Operates in well under a second | Survives for several seconds |
| 10 × In and above | Current-limiting, sub-cycle | Current-limiting, sub-cycle |
At 6 × In the two behaviours diverge by an order of magnitude, which is exactly where a direct-on-line start sits. This is why a distribution fuse at the motor rating does not merely age — it operates on the first start.
It also explains the opposite error: fitting a motor fuse into a distribution position. Above about 3 × In the motor fuse is slower than the cable damage curve allows, so a cable fault may be cleared by the cable failing first.
The 690 V series carry high breaking capacity — the CT range is quoted at 90 kA RMS symmetrical and 40 kA at 500 V DC. That figure is far above the fault level in most British distribution boards, which is why the smaller 240 V series exist at all: they are cheaper and smaller for the lower fault levels found on the LV side of a 240 V distribution board.
The selection question is therefore not “what is the highest breaking capacity available” but “what is the fault level at this point”. A 6 kA fault level in a final distribution board does not justify a 90 kA fuse, and the 90 kA part may not fit the board's holders.
Most BS88 orders are replacements, not new designs, and in a replacement the original part number is often illegible. The working method is:
Step 4 is where a replacement goes wrong. A panel with a motor starter and a BS88 fuse may have been fitted with a distribution fuse by a previous contractor, and copying that choice perpetuates the error. The visual inspection that distinguishes them — a motor fuse in a starter, a distribution fuse in a busbar chamber — is not always obvious, and the circuit function is the reliable indicator.
Is BS88 the same as IEC 60269?
No. BS88 is the British standard; IEC 60269 is the international one. Many Bussmann parts are tested to both, but the mechanical envelope differs and they are not interchangeable.
Can I replace a 240 V LET with a 690 V ET at the same current?
Electrically the higher voltage rating is acceptable on a 240 V system, and the body size is the same. Check the breaking capacity and the DC rating, which may differ.
Why do so many series exist at the same current?
Because the matrix multiplies three variables — voltage, breaking capacity and characteristic — and the manufacturer offers the useful combinations rather than all of them.
Which series for a DC battery at 400 V?
FM or FMM at 450 V d.c. MT and MMT stop at 350 V, and the 500 V group is rated for rectifier and DC distribution duty rather than battery.
Do BS88 fuses need derating in enclosures?
Yes, as with any fuse. BS88 bodies are ceramic and tolerate heat well, but the holder and the terminals set the practical limit.
BS88 is one mechanical standard carrying thirteen electrical products. Choose the series by voltage class and duty, the rating by current and starting characteristic, and the breaking capacity by the fault level at the installation point. Then confirm the DC rating if the circuit is DC, because that is the number the a.c. voltage hides.
The matrix looks redundant until the duty is considered. At 180 A, FM, MMT and LMT are all available and only one of them is right for a given circuit — and the difference is not in the ampere rating, but in what the fuse is expected to survive.