Bussmann BS88 Fuse Selection: All 13 Series Compared (LCT to MMT)

Time:2026-11-24   Author:As Beam   Browse:

British Standard Fuses · Selection Matrix

Thirteen Bussmann BS88 series share one mounting standard and one set of body sizes, yet they are not interchangeable: voltage class, breaking capacity, element design and DC rating all differ. This guide maps all thirteen — LCT, LET, LMT, LMMT, CT, ET, FE, EET, FEE, FM, FMM, MT and MMT — against current range, voltage and duty, so the right series is chosen before the part number.

Anyone who has opened a British panel has met the BS88 fuse: a white ceramic body with offset bolted tags, held between two studs, and a catalogue that lists more variants for the same current than any other family in the Bussmann range. At 100 A, for example, the range offers ET, FE, FEE, LMT, MT and MMT parts, all fitting similar holders, all rated differently.

The reason is history. BS88 grew out of British industrial practice, where the fuse had to serve motor circuits, distribution boards and DC battery systems with one mechanical format. The format was standardised; the electrical duties were not. Understanding the resulting matrix is the difference between a correct selection and a fuse that operates on every motor start.

What BS88 defines and what it does not

BS88 standardises the mechanical envelope: body diameter, overall length, tag offset, tag hole diameter and centre distance. It does not standardise the electrical characteristic, which is why the standard has parts:

  • BS88 Part 2 — general industrial fuses (gG type duty), for cable and distribution protection.
  • BS88 Part 4 — semiconductor devices, fast-acting, for rectifiers and DC links.
  • BS88 Part 6 — fuses for motor circuits, with a characteristic that tolerates starting current.

A fuse marked to one part cannot be assumed to meet another. A Part 6 motor fuse in a distribution position will not protect the cable properly; a Part 2 fuse in a motor circuit will operate on starting current. Both fit the same holder.

The single most useful rule in this family: the part number tells you the current and the series; the series tells you the voltage and duty; the standard part tells you what the fuse is allowed to protect. All three are needed before ordering.

The thirteen series at a glance

The table below lists all thirteen series with their published voltage class and the current range actually available in each. It is the matrix that should be consulted first.

SeriesVoltageCurrent rangeTypical duty
LCT240 V a.c. / 150 V d.c. (IEC)6 – 20 ASmall distribution, control circuits
LET280 V a.c. / 150 V d.c. (UL)25 – 180 ADistribution, higher breaking capacity
LMT240 V a.c.160 – 450 AHeavy distribution, large cable
LMMT240 V a.c.400 – 900 ASub-main protection
CT690 V a.c. / 500 V d.c. (IEC)6 – 20 AHigh breaking capacity, 90 kA RMS sym
ET690 V a.c. / 500 V d.c. (IEC)25 – 80 AGeneral industrial at 690 V
FE690 V a.c. / 500 V d.c. (IEC)35 – 100 ADistribution at 690 V
EET690 V a.c. / 500 V d.c. (IEC)90 – 160 ADistribution at 690 V
FEE690 V a.c. / 500 V d.c. (IEC)100 – 200 ADistribution at 690 V
FM690 V a.c. / 450 V d.c. (IEC)180 – 350 AMotor circuits, high current
FMM690 V a.c. / 450 V d.c. (IEC)400 – 700 AMotor circuits, very high current
MT690 V a.c. / 350 V d.c. (IEC)160 – 355 AMotor protection with DC rating
MMT690 V a.c. / 350–450 V d.c.180 – 710 AMotor protection, largest body

Two patterns stand out. First, the current ranges overlap heavily: between 160 A and 200 A there are six different series available. Second, the DC rating is not uniform — 150 V for the LCT/LET pair, 350 V for MT/MMT, 450 V for FM/FMM, 500 V for the CT/ET/FE group. That spread matters more than it looks, and it is where most DC misapplications originate.

Why thirteen series and not three

Three variables generate the matrix: voltage class, breaking capacity and element characteristic. Each series is a fixed combination, and the manufacturer does not offer every combination in every size.

VariableOptions within BS88Effect on selection
Voltage240 V, 280 V, 690 V a.c.; 150 to 500 V d.c.Sets the minimum series; a 690 V system cannot use a 240 V part
Breaking capacityFrom 40 kA d.c. up to 90 kA RMS symmetrical (CT)Set by prospective fault current at the installation point
CharacteristicgG distribution, motor-rated (Part 6), fast (Part 4)Determines whether the fuse tolerates starting current

The practical consequence is that a specification of “BS88, 100 A, 690 V” is still ambiguous: it could be FE, FEE, EET or one of the motor-rated series at that current. The distinguishing question is not electrical at all — it is what the fuse is protecting.

Motor circuits: why the series matters more than the current

A motor starting direct-on-line draws five to seven times its rated current for several seconds. A gG distribution fuse at the motor's rated current will operate during that start. The motor-rated series (FM, FMM, MT, MMT) use an element with a delayed characteristic that tolerates the start while still protecting the cable.

Selecting a motor fuse therefore starts from the motor's full-load current, not from the cable ampacity:

  1. Take the motor full-load current from the nameplate at the actual supply voltage.
  2. Choose the series by voltage and by the duty — motor-rated, not gG.
  3. Select the rating so that the fuse carries the starting current for the acceleration time with margin, using the time-current curve rather than a multiplier.
  4. Check the cable is protected at the selected rating; if not, the cable is undersized for the motor.
  5. Check breaking capacity against the fault level at the motor terminals.

Step 3 is where a multiplier is often used instead of the curve, and it is the step that fails. A “1.75 × FLC” rule works for many small motors and fails for high-inertia loads with long acceleration, where the fuse must be larger or the starting method changed.

DC applications: the 150 / 350 / 450 / 500 V spread

BS88 fuses carry DC ratings, and they differ sharply between series. This is the area where a plausible-looking substitution produces a fuse that cannot clear a DC fault.

Series groupDC ratingSuitable for
LCT, LET150 V d.c.24/48/110 V battery systems, control supplies
MT, MMT350 V d.c.Telecom and UPS battery strings up to 350 V
FM, FMM450 V d.c.Higher-voltage battery and DC link circuits
CT, ET, FE, EET, FEE500 V d.c.DC distribution up to 500 V, rectifier outputs

None of these is a 1000 V DC fuse. A BS88 part in a modern 800 V or 1000 V battery system is outside its DC rating no matter which series is chosen — that application belongs to the square-body DC families, not to BS88. The distinction is easy to miss because the a.c. rating (690 V) looks higher than the DC system voltage.

Never read the a.c. voltage as a d.c. voltage. A 690 V a.c. BS88 part may have a 350 V or 450 V d.c. rating. The d.c. figure is the one that applies to a battery or DC link.

Worked example: 415 V motor, 45 kW

A 45 kW four-pole motor at 415 V draws about 80 A full load, with a direct-on-line starting current around 480 A for six seconds. The fault level at the motor terminals is 25 kA.

Step 1: duty is motor starting, so a motor-rated series is required — not gG. Step 2: 415 V is within the 690 V class, so the ET or MT series are candidates by voltage. Step 3: at 80 A the available motor-rated parts include ET and MT; the choice depends on acceleration time. A six-second start at 6 × FLC rules out the smallest sizes and points to a rating around 100 A in the motor series, which in this range is FE or MT.

Step 4: cable. A 35 mm² cable at 100 A is protected comfortably. Step 5: breaking capacity. The 25 kA fault level is well within the 690 V series, which are rated far above that.

The interesting part is step 3: the same 80 A motor could be protected by three different series, and the decision comes from the acceleration time, not from the current. That is why the time-current curve, not the ampere rating, settles motor applications.

Worked example: 110 V DC battery circuit

A substation battery at 110 V DC, 60 A continuous, with a prospective short-circuit current of 8 kA. The existing panel uses BS88 fuses in a bolted holder.

Step 1: 110 V DC is within the 150 V d.c. rating of LCT and LET, so those series are candidates. Step 2: at 60 A, LCT stops at 20 A, so LET is the series — its range runs to 180 A. Step 3: breaking capacity — 8 kA is modest and the LET series covers it. Step 4: the holder is the same bolted pattern, so the replacement is mechanically straightforward.

Now suppose the battery is upgraded to 220 V DC. LET's 150 V d.c. rating is exceeded, and the correct move is to a series with a higher DC rating — MT or MMT at 350 V d.c. — which changes the body size and therefore the holder. The electrical current is unchanged at 60 A; the mechanical envelope is not.

Body sizes and what they imply

BS88 bodies come in the familiar lettered sizes (A1 through A4 in the British convention), and the size follows the current rather than the voltage. Practical implications:

  • Same holder, different series. Because the mechanical envelope is standardised, an ET and an FE at the same current often fit the same holder. This is convenient for spares and dangerous for substitution, because the wrong series drops straight in.
  • Tag offset is part of the standard. Offset tags mean the fuse can only be inserted one way; reversing it will not make contact.
  • Body length grows with current, not voltage. A 690 V 20 A part and a 240 V 20 A part are the same size. This is the opposite of the square-body 170M range, where voltage drives length.

That last point is the essential difference between the two families and worth stating plainly: in BS88, voltage class does not change the body size; in the 170M square-body range it does. Engineers who work with both regularly apply the wrong intuition in one direction or the other.

Part 2 versus Part 6 in numbers

The difference between a distribution fuse and a motor fuse is a factor of roughly two in operating time at the same multiple of rated current. It is worth seeing the shape of the difference rather than the rule.

Multiple of ratingDistribution (Part 2) behaviourMotor (Part 6) behaviour
1.5 × InOperates within minutesDoes not operate (below the minimum operating current)
3 × InOperates in secondsOperates in tens of seconds
6 × InOperates in well under a secondSurvives for several seconds
10 × In and aboveCurrent-limiting, sub-cycleCurrent-limiting, sub-cycle

At 6 × In the two behaviours diverge by an order of magnitude, which is exactly where a direct-on-line start sits. This is why a distribution fuse at the motor rating does not merely age — it operates on the first start.

It also explains the opposite error: fitting a motor fuse into a distribution position. Above about 3 × In the motor fuse is slower than the cable damage curve allows, so a cable fault may be cleared by the cable failing first.

Breaking capacity in practice

The 690 V series carry high breaking capacity — the CT range is quoted at 90 kA RMS symmetrical and 40 kA at 500 V DC. That figure is far above the fault level in most British distribution boards, which is why the smaller 240 V series exist at all: they are cheaper and smaller for the lower fault levels found on the LV side of a 240 V distribution board.

The selection question is therefore not “what is the highest breaking capacity available” but “what is the fault level at this point”. A 6 kA fault level in a final distribution board does not justify a 90 kA fuse, and the 90 kA part may not fit the board's holders.

Replacing fuses in an installed panel

Most BS88 orders are replacements, not new designs, and in a replacement the original part number is often illegible. The working method is:

  1. Measure the body — diameter and overall length — to establish the BS88 size.
  2. Measure the tag offset and hole diameter, then confirm candidates fit the existing studs.
  3. Infer the voltage class from the panel's supply voltage and from any marking that survives.
  4. Infer the duty from the circuit: motor, distribution, or DC.
  5. Select the series from the matrix, then the rating from the load.

Step 4 is where a replacement goes wrong. A panel with a motor starter and a BS88 fuse may have been fitted with a distribution fuse by a previous contractor, and copying that choice perpetuates the error. The visual inspection that distinguishes them — a motor fuse in a starter, a distribution fuse in a busbar chamber — is not always obvious, and the circuit function is the reliable indicator.

Common mistakes

  1. Specifying by current and voltage only. Six series overlap at 160–200 A; the duty decides which one.
  2. Using a gG part in a motor circuit. It will operate on start, and the “solution” of increasing the rating then leaves the cable unprotected.
  3. Reading 690 V a.c. as a DC rating. The DC figures are 150 to 500 V depending on series.
  4. Assuming BS88 is obsolete. It remains the standard format in British-origin equipment and in many installed bases; the installed base is exactly where replacements are ordered.
  5. Replacing a Part 4 semiconductor fuse with a Part 2 part. Both fit; only one protects the semiconductor.
  6. Ignoring the tag offset. The fuse will physically enter the holder only one way, and forcing it damages the contact.

FAQ

Is BS88 the same as IEC 60269?

No. BS88 is the British standard; IEC 60269 is the international one. Many Bussmann parts are tested to both, but the mechanical envelope differs and they are not interchangeable.

Can I replace a 240 V LET with a 690 V ET at the same current?

Electrically the higher voltage rating is acceptable on a 240 V system, and the body size is the same. Check the breaking capacity and the DC rating, which may differ.

Why do so many series exist at the same current?

Because the matrix multiplies three variables — voltage, breaking capacity and characteristic — and the manufacturer offers the useful combinations rather than all of them.

Which series for a DC battery at 400 V?

FM or FMM at 450 V d.c. MT and MMT stop at 350 V, and the 500 V group is rated for rectifier and DC distribution duty rather than battery.

Do BS88 fuses need derating in enclosures?

Yes, as with any fuse. BS88 bodies are ceramic and tolerate heat well, but the holder and the terminals set the practical limit.

Summary

BS88 is one mechanical standard carrying thirteen electrical products. Choose the series by voltage class and duty, the rating by current and starting characteristic, and the breaking capacity by the fault level at the installation point. Then confirm the DC rating if the circuit is DC, because that is the number the a.c. voltage hides.

The matrix looks redundant until the duty is considered. At 180 A, FM, MMT and LMT are all available and only one of them is right for a given circuit — and the difference is not in the ampere rating, but in what the fuse is expected to survive.