One of the most common and dangerous mistakes in electrical design is assuming a fuse rated for a certain AC voltage works at the same DC voltage. It doesn't. In fact, a fuse rated 690VAC might carry no DC rating at all — and using it in a 690VDC circuit could result in a failure to interrupt, with catastrophic consequences.
This guide explains the physics behind DC fuse design, the concept of time constant, and how to select DC fuses correctly from the Bussmann range.

The fundamental difference is the zero crossing.
In a 50Hz AC system, the current passes through zero 100 times per second. At each zero crossing:
The arc momentarily extinguishes
The dielectric strength of the gap begins to recover
If the recovery is faster than the voltage rise, the arc stays out
This natural zero-crossing gives AC fuses a "free" opportunity to extinguish the arc twice per cycle. AC quenching is relatively easy.
DC current flows continuously in one direction. There is no zero crossing. The arc persists as long as:
Current continues to flow
Voltage remains present
The gap's dielectric strength is insufficient
A DC fuse must force the arc to extinguish by: 1. Raising the arc voltage above the system voltage (via multiple series break points) 2. Physically cooling and splitting the arc (via quartz sand) 3. The arc voltage overcoming the system voltage, forcing current to zero
This is why DC-rated fuses have more series break points and different sand packing than AC fuses of the same voltage class.
A fuse rated 690VAC is NOT automatically rated 690VDC.
Common misreadings:
| Fuse marking | Usable DC voltage | Note |
|---|---|---|
| 690VAC only | None | No DC rating — do not use in DC |
| 690VAC / 250VDC | 250VDC | DC rating is separate and lower |
| 690VAC / 690VDC | 690VDC | Explicit dual rating |
| 1000VDC (DC-only) | 1000VDC | Purpose-built DC fuse |
Rule: Always look for an explicit DC voltage rating in the datasheet. If there's no DC rating, the fuse is not for DC use.
In DC circuits, the time constant (τ) describes how fast fault current rises. It's defined as L/R (inductance divided by resistance).
τ = L / R
A fuse's DC breaking capacity is specified at a particular time constant. Why? Because a circuit with a large time constant (high inductance) stores more magnetic energy, which must be absorbed during interruption.
| Circuit Type | Typical τ | Notes |
|---|---|---|
| Battery circuits | 1–5ms | Low inductance, low τ |
| PV strings | 1–3ms | Low inductance |
| EV battery pack | 2–5ms | Low inductance |
| BESS rack | 4.5ms | Reference value for BSF |
| Traction converter | 5–15ms | Higher inductance |
| Third-rail | 10–30ms | Very high inductance |
| DC motor circuit | 10–50ms | Field inductance dominates |
The implication: A fuse rated 100kA at τ = 4.5ms may only be rated 40kA at τ = 15ms. Always verify the time constant at which the breaking capacity is specified and compare to your circuit.
| Class | Meaning | Typical DC Use |
|---|---|---|
| gPV | Full-range, photovoltaic | PV strings and arrays |
| gBat | Full-range, battery | BESS, EV battery |
| aR / gR | Semiconductor, high-speed | DC links, inverters |
| gG (DC-rated) | General purpose | DC distribution |
| Series | Voltage | Current | Class | Application |
|---|---|---|---|---|
| EVH | 70VDC | 5–150A | — | Auxiliary DC |
| EVR10 | 500VDC | 50–100A | — | Small EV |
| EVR30 | 500VDC | 125–300A | — | Main EV |
| EVR50 | 500VDC | 315–500A | — | Commercial EV |
| EVK30 | 1000VDC | 100–300A | — | 800V platform |
| EVK60 | 1000VDC | 200–500A | — | Heavy EV |
| EVP20 | 750VDC | 15–60A | — | OBC input |
| XEV30 | 500VDC | — | — | Crossover designs |
| Series | Voltage | Current | Application |
|---|---|---|---|
| PVM-10x85 | 1000/1500VDC | 1–30A | String protection |
| PV-A14F/L | 1000/1500VDC | 15–32A | Large strings |
| PV-ANH | 1000/1500VDC | 32–630A | Array protection |
| PV15M-H | 1500VDC | 63–630A | Utility-scale |
| Series | Voltage | Current | Application |
|---|---|---|---|
| BSF | 1000VDC | 63–400A | Rack protection, τ = 4.5ms |
| ESS2 | 1500VDC | 100–450A | Utility BESS |
| ESS5 | 1500VDC | 630–1800A | DC bus |
| H50ESS | PCB | Low | Module level |
| Series | Voltage | Application |
|---|---|---|
| CBX000S | 800VDC | 60kW DC chargers |
| CBX01S | 1000VDC | 120kW+ DC chargers |
| Series | Voltage | Application |
|---|---|---|
| 170M52xx | 1500VDC | Solar/ESS inverters |
| 170M60xx | 2000VDC | Railway traction |
| FWE | 1000VDC | DC semiconductor |
| LRC750 | 750VDC | Third rail |
1. Determine system maximum DC voltage
↓
2. Determine circuit time constant (L/R)
↓
3. Calculate continuous current
↓
4. Apply safety factor (1.25 typical)
↓
5. Select DC-rated fuse with:
- Voltage rating ≥ system voltage
- Current rating ≥ derated load current
- Breaking capacity at your τ ≥ fault current
- Correct operating class (gPV/gBat/aR)
↓
6. Select matching DC-rated holder
↓
7. Verify temperature derating
System:- Battery: 400V nominal, 450VDC maximum - Continuous current: 220A - Fault current: 18kA - Circuit time constant: 3ms
Selection:1. Voltage: 450VDC max → need ≥ 500VDC rated 2. Current: 220A × 1.25 = 275A → 300A 3. Class: EV battery → use EVR series 4. Selected: EVR30-300 (500VDC, 300A) 5. Verify: breaking capacity at 3ms ≥ 18kA ✓
System:- Battery rack: 1000VDC, 250A continuous - Fault current: 40kA - Time constant: 4.5ms
Selection:1. Voltage: 1000VDC → BSF series (1000VDC, gBat) 2. Current: 250A × 1.25 = 313A → 315A 3. Selected: BSF-315A4. Verify: BSF breaking capacity = 100kA at τ = 4.5ms > 40kA ✓
System:- Sub-array: 1500VDC, 200A - Fault current: 25kA - Time constant: 2ms
Selection:1. Voltage: 1500VDC → PV15M or PV-ANH (1500VDC) 2. Current: 200A × 1.25 = 250A → 315A 3. Selected: PV15M-315A-H4. Verify: breaking capacity at 2ms ≥ 25kA ✓
DC fuses require DC-rated holders. Using an AC holder compromises arc containment and insulation.
| Fuse Series | DC-Rated Holder |
|---|---|
| PVM-10x85 | CHPV15L85 |
| PV-ANH | SD-D-PV / SD-S-PV |
| BSF | SD-D-PV / SD3-SC |
| EVR/EVK | Integrated or panel-mount |
| CBX | Panel-mount charger holders |
Q: Can I derate an AC fuse for DC use?A: No. Derating from AC to DC is not a valid approach. You must use a fuse with an explicit DC rating. Some manufacturers publish a DC rating that's a fraction of the AC rating — but if it's not published, the fuse has no DC rating.
Q: What's the difference between gPV and gBat?A: gPV (IEC 60269-6) is for photovoltaic applications — tested for PV fault profiles and bi-directional currents. gBat (IEC 60269-7 draft) is for battery storage — tested for low overcurrent interruption (1.3–2× rated). A gPV fuse may not interrupt a battery's low-overcurrent fault; a gBat fuse can.
Q: Why does time constant matter so much?A: Higher time constant = more inductive energy to absorb during interruption = harder to extinguish the arc. A fuse's stated breaking capacity is only valid at the specified time constant.
Q: Are DC fuses more expensive than AC fuses?A: Generally yes, because they require more internal break points and more precise arc management. The premium reflects the harder engineering problem.