New industry Technology regarding to Bussmann fuse, ABB breakers, Amphenol connectors, HPS transformers, etc.

Quick answer: Metering CT classes such as 0.2, 0.2S, 0.5 and 0.5S prioritize accuracy around normal load. Protection classes such as 5P10 or 5P20 must reproduce fault current up to an accuracy-limit factor. PX/Class X is specified from excitation and knee-point requirements for special protection schemes. |
A current transformer scales primary current to a standardized secondary value, commonly 5 A or 1 A. A complete CT specification includes ratio, secondary current, accuracy class, rated burden, frequency, insulation level, short-time current, core purpose and physical construction. The class cannot be selected independently of the connected meter or relay and its wiring.
Marking | Purpose | Interpretation | Typical application |
0.2 / 0.2S | Precision metering | Tighter ratio and phase error limits; S class extends specified performance at low current | Revenue or high-accuracy energy measurement |
0.5 / 0.5S | General metering | Common monitoring accuracy; S class supports a wider low-current range | Building/industrial energy monitoring |
1.0 | Indication | Lower precision than 0.5 or 0.2 | Ammeters and non-critical monitoring |
5P10 | Protection | Composite error limit 5% at 10 x rated current at rated burden | Overcurrent/earth-fault protection |
5P20 | Protection | Composite error limit 5% at 20 x rated current at rated burden | Higher fault-current reproduction requirement |
10P10 | Protection | Composite error limit 10% at ALF 10 | Protection where this accuracy is acceptable |
PX / Class X | Special protection | Defined by knee-point voltage, excitation current and winding resistance | Differential, restricted earth fault and special schemes |
Do not interpret Class 0.5 as a universal +/-0.5% statement under every current and burden condition. IEC accuracy limits depend on current percentage, burden and class. Use the standard and the manufacturer's certificate for the specific CT.
CT burden is the total secondary load in volt-amperes at rated secondary current. It includes the meter or relay input plus both conductors between the CT and device. Excess burden increases ratio and phase error and can cause a protection CT to saturate earlier.
Example: A 5 A secondary with 0.08 ohm total loop resistance creates I^2R = 5^2 x 0.08 = 2 VA of wiring burden. If the meter adds 0.5 VA, the total is 2.5 VA. A CT rated 5 VA has margin; a 2.5 VA CT would be at its nominal burden before connector and temperature effects. |
A 1 A secondary reduces wiring burden by a factor of 25 for the same loop resistance because burden scales with current squared. It is often preferable for long cable runs, provided the relay or meter accepts a 1 A input.
ASBEAM lists Socomec DIRIS A10 references 48250400 and 48250401 as compatible with 5 A CT inputs; 48250401 is presented with RS485/Modbus communication. When pairing a CT with either model, specify a 5 A secondary, the primary ratio (for example 200/5 A or 800/5 A), a metering class such as 0.5 or 0.5S where appropriate, and enough VA burden for the instrument plus leads. The meter model does not determine the CT ratio; the maximum load current does.
1. Define purpose: revenue metering, general monitoring, overcurrent protection, differential protection or a dual-core combination.
2. Select primary ratio so normal maximum current uses a useful portion of the CT range without chronic over-ranging.
3. Match the secondary current to the meter or relay input: 1 A or 5 A.
4. Choose the accuracy class from the purpose and governing standard; use S-class metering where low-load accuracy matters.
5. Calculate total burden from instrument input, lead length/gauge, terminals and test switches, then choose a rated burden with suitable margin.
6. For protection CTs, select ALF such as 5P10 or 5P20 from maximum fault current and relay requirements; confirm saturation performance.
7. For PX/Class X, specify knee-point voltage, excitation current limit and secondary winding resistance from the protection study.
8. Confirm window/busbar size, mounting, insulation level, frequency, short-time thermal current and dynamic current ratings.
9. Check secondary earthing, terminal shorting facilities and safe test procedures. Never open-circuit an energized CT secondary.
Specification | Meaning | Typical use |
400/5 A, 5 VA, Class 0.5 | 400 A primary gives 5 A secondary; 5 VA rated burden | General metering with short leads |
800/5 A, 10 VA, Class 0.5S | S-class metering over a wider current range | Energy monitoring with variable load |
600/1 A, 10 VA, 5P20 | Protection CT, 5% composite error at ALF 20 | Long lead run to overcurrent relay |
1200/1 A, PX, Vk >= project value | Special protection core defined by excitation data | Differential or REF protection |
It is a protection CT class with a 5% composite-error limit at an accuracy limit factor of 10, at rated burden and stated conditions.
It provides specified accuracy over a wider low-current range, which is valuable for variable-load metering. Cost, burden and the measurement objective still matter.
Sometimes, but separate metering and protection cores are often specified because their saturation objectives differ. Follow the protection and metering design.
Not unless the exact meter/reference supports and is configured for 1 A. The cited ASBEAM product pages describe 5 A CT compatibility.
CT accuracy is a system property involving the CT, burden, wiring and connected device. Specify ratio, 1 A/5 A secondary, class, VA burden and protection saturation performance together. A model such as DIRIS A10 48250401 helps define the instrument interface, but not the entire CT specification.
For a CT and meter pairing review, send ASBEAM the one-line diagram, maximum load, fault current, lead length/gauge, required meter or relay model and desired accuracy class.
• ASBEAM - Socomec DIRIS A10 48250401
• ASBEAM - Socomec DIRIS A10 48250400
New industry Technology regarding to Bussmann fuse, ABB breakers, Amphenol connectors, HPS transformers, etc.