In need of urgent assistance? Call +86-13427815151 

新闻与咨询

New industry Technology regarding to Bussmann fuse, ABB breakers, Amphenol connectors, HPS transformers, etc. 

Current Transformer Accuracy Classes: Metering vs Protection Selection

Time:2026-09-04   Author:As Beam   Browse:

Current Transformer Accuracy Classes: Metering vs Protection Selection

Quick answer: Metering CT classes such as 0.2, 0.2S, 0.5 and 0.5S prioritize accuracy around normal load. Protection classes such as 5P10 or 5P20 must reproduce fault current up to an accuracy-limit factor. PX/Class X is specified from excitation and knee-point requirements for special protection schemes.

 

A current transformer scales primary current to a standardized secondary value, commonly 5 A or 1 A. A complete CT specification includes ratio, secondary current, accuracy class, rated burden, frequency, insulation level, short-time current, core purpose and physical construction. The class cannot be selected independently of the connected meter or relay and its wiring.

Metering and protection classes

Marking

Purpose

Interpretation

Typical application

0.2 / 0.2S

Precision metering

Tighter ratio and phase error limits; S class extends specified performance at low current

Revenue or high-accuracy energy measurement

0.5 / 0.5S

General metering

Common monitoring accuracy; S class supports a wider low-current range

Building/industrial energy monitoring

1.0

Indication

Lower precision than 0.5 or 0.2

Ammeters and non-critical monitoring

5P10

Protection

Composite error limit 5% at 10 x rated current at rated burden

Overcurrent/earth-fault protection

5P20

Protection

Composite error limit 5% at 20 x rated current at rated burden

Higher fault-current reproduction requirement

10P10

Protection

Composite error limit 10% at ALF 10

Protection where this accuracy is acceptable

PX / Class X

Special protection

Defined by knee-point voltage, excitation current and winding resistance

Differential, restricted earth fault and special schemes

 

Do not interpret Class 0.5 as a universal +/-0.5% statement under every current and burden condition. IEC accuracy limits depend on current percentage, burden and class. Use the standard and the manufacturer's certificate for the specific CT.

Burden: the part most specifications miss

CT burden is the total secondary load in volt-amperes at rated secondary current. It includes the meter or relay input plus both conductors between the CT and device. Excess burden increases ratio and phase error and can cause a protection CT to saturate earlier.

Example: A 5 A secondary with 0.08 ohm total loop resistance creates I^2R = 5^2 x 0.08 = 2 VA of wiring burden. If the meter adds 0.5 VA, the total is 2.5 VA. A CT rated 5 VA has margin; a 2.5 VA CT would be at its nominal burden before connector and temperature effects.

 

A 1 A secondary reduces wiring burden by a factor of 25 for the same loop resistance because burden scales with current squared. It is often preferable for long cable runs, provided the relay or meter accepts a 1 A input.

Model pairing example: Socomec DIRIS A10

ASBEAM lists Socomec DIRIS A10 references 48250400 and 48250401 as compatible with 5 A CT inputs; 48250401 is presented with RS485/Modbus communication. When pairing a CT with either model, specify a 5 A secondary, the primary ratio (for example 200/5 A or 800/5 A), a metering class such as 0.5 or 0.5S where appropriate, and enough VA burden for the instrument plus leads. The meter model does not determine the CT ratio; the maximum load current does.

Complete CT selection process

1. Define purpose: revenue metering, general monitoring, overcurrent protection, differential protection or a dual-core combination.

2. Select primary ratio so normal maximum current uses a useful portion of the CT range without chronic over-ranging.

3. Match the secondary current to the meter or relay input: 1 A or 5 A.

4. Choose the accuracy class from the purpose and governing standard; use S-class metering where low-load accuracy matters.

5. Calculate total burden from instrument input, lead length/gauge, terminals and test switches, then choose a rated burden with suitable margin.

6. For protection CTs, select ALF such as 5P10 or 5P20 from maximum fault current and relay requirements; confirm saturation performance.

7. For PX/Class X, specify knee-point voltage, excitation current limit and secondary winding resistance from the protection study.

8. Confirm window/busbar size, mounting, insulation level, frequency, short-time thermal current and dynamic current ratings.

9. Check secondary earthing, terminal shorting facilities and safe test procedures. Never open-circuit an energized CT secondary.

Common specification examples

Specification

Meaning

Typical use

400/5 A, 5 VA, Class 0.5

400 A primary gives 5 A secondary; 5 VA rated burden

General metering with short leads

800/5 A, 10 VA, Class 0.5S

S-class metering over a wider current range

Energy monitoring with variable load

600/1 A, 10 VA, 5P20

Protection CT, 5% composite error at ALF 20

Long lead run to overcurrent relay

1200/1 A, PX, Vk >= project value

Special protection core defined by excitation data

Differential or REF protection

 

Frequently Asked Questions

What does 5P10 mean?

It is a protection CT class with a 5% composite-error limit at an accuracy limit factor of 10, at rated burden and stated conditions.

Is 0.5S always better than 0.5?

It provides specified accuracy over a wider low-current range, which is valuable for variable-load metering. Cost, burden and the measurement objective still matter.

Can one CT core feed both a meter and a protection relay?

Sometimes, but separate metering and protection cores are often specified because their saturation objectives differ. Follow the protection and metering design.

Can I connect a 1 A CT to a DIRIS A10 listed for 5 A CT input?

Not unless the exact meter/reference supports and is configured for 1 A. The cited ASBEAM product pages describe 5 A CT compatibility.

Bottom line

CT accuracy is a system property involving the CT, burden, wiring and connected device. Specify ratio, 1 A/5 A secondary, class, VA burden and protection saturation performance together. A model such as DIRIS A10 48250401 helps define the instrument interface, but not the entire CT specification.

For a CT and meter pairing review, send ASBEAM the one-line diagram, maximum load, fault current, lead length/gauge, required meter or relay model and desired accuracy class.

Technical references

ASBEAM - Socomec DIRIS A10 48250401

ASBEAM - Socomec DIRIS A10 48250400



New industry Technology regarding to Bussmann fuse, ABB breakers, Amphenol connectors, HPS transformers, etc. 


TAG:   current transformer accuracy class  CT accuracy class accuracy limit factor protection CT