Both FWH and FWP fuses use a cylindrical body with ferrule (cap) terminals -- the same form factor as standard IEC 60269-4 semiconductor fuses. This cylindrical ferrule design offers practical advantages: compatibility with standard DIN rail clips and busbar-mounted fuse holders; uniform heat dissipation without hot spots; proven automotive vibration and thermal cycling performance meeting ISO 16750 requirements; and field replaceability by trained technicians without specialized tools.

FWH Series -- 500 Vdc, 50 kA
Part Number | Rating | Voltage | IR |
FWH-35C | 35A | 500 Vdc | 50 kA |
FWH-100C | 100A | 500 Vdc | 50 kA |
FWH-200C | 200A | 500 Vdc | 50 kA |
FWH-350C | 350A | 500 Vdc | 50 kA |
FWH-500C | 500A | 500 Vdc | 50 kA |
FWH-800C | 800A | 500 Vdc | 50 kA |
FWP Series -- 700 Vdc, 50 kA
Part Number | Rating | Voltage | IR |
FWP-35C | 35A | 700 Vdc | 50 kA |
FWP-125C | 125A | 700 Vdc | 50 kA |
FWP-250C | 250A | 700 Vdc | 50 kA |
FWP-400C | 400A | 700 Vdc | 50 kA |
FWP-600C | 600A | 700 Vdc | 50 kA |
FWJ Series -- 800 Vdc, 50 kA (Imperial Ferrule)
Part Number | Rating | Voltage | IR |
FWJ-35A | 35A | 800 Vdc | 50 kA |
FWJ-125A | 125A | 800 Vdc | 50 kA |
FWJ-250A | 250A | 800 Vdc | 50 kA |
FWJ-400A | 400A | 800 Vdc | 50 kA |
FWJ-600A | 600A | 800 Vdc | 50 kA |
Select the lowest voltage family that provides adequate margin above your maximum system voltage. For a 400V nominal system (approximately 460V peak at full charge), FWH at 500 Vdc provides 8.7% voltage margin -- acceptable for most applications. For a 600V nominal system (approximately 690V peak), FWP at 700 Vdc provides only 1.4% margin -- marginal for some applications. FWJ at 800 Vdc provides 15.9% margin for the same 600V system, often preferred for robust protection. The FWJ uses imperial (inch-based) ferrule dimensions, which may affect holder compatibility compared to the metric FWH-C and FWP-C series. Verify holder compatibility before specifying.
In EV: FWH-C is used for OBC AC input protection (500V rating provides adequate margin above 400Vac input), DC-DC converter input/output protection, and low-voltage battery pack protection in 200-400V architectures. In ESS: FWH-C for battery rack combiner protection (500V tier) and PCS DC side protection for 500V-class BESS. FWP for 600-700V battery bus protection where FWH's 500V rating is insufficient. FWJ for 800V battery bus protection in a ferrule form factor where the 170M square-body size is too large.