New industry Technology regarding to Bussmann fuse, ABB breakers, Amphenol connectors, HPS transformers, etc.
Choosing the wrong surge protective device is a surprisingly common mistake. An undersized unit may fail during a major surge event. An oversized unit wastes budget without meaningfully better protection. A device with the wrong voltage rating may either fail to clamp effectively or operate incorrectly under normal conditions. This guide walks through the technical fundamentals using the Eaton NSP Series as a concrete reference.

Type | Test Waveform | Key Parameter | Where to Install |
Type 1 | 10/350μs | Iimp (kA) | Main service entrance with external LPS |
Type 2 | 8/20μs | In / Imax (kA) | Sub-distribution boards, downstream panels |
Type 1+2 | 10/350μs + 8/20μs | Iimp + Imax | Combined main/sub board; space-limited installs |
Selection Rule: If your facility has a dedicated lightning protection down-conductor (per IEC 62305), install a Type 1 or T1+T2 device at the main switchboard and Type 2 at every downstream sub-distribution panel.
The Uc must always be ≥ Uc_system x 1.1. For standard 230V/400V three-phase TN/TT systems:
Protection Mode | Uc Recommendation | NSP Rating |
L-PE (Line to Earth) | ≥ 1.1 x 230V = 253V | 385Vac |
L-N (Line to Neutral) | ≥ 1.1 x 230V = 253V | 385Vac |
N-PE (Neutral to Earth) | Neutral-ground variation | 255–260Vac |
Solar PV (1000V string) | ≤ 1000Vdc | 1300Vdc module |
Solar PV (1500V string) | ≤ 1500Vdc | 1500Vdc T1+T2 |
Wind 440V generator | 440Vac system | 440Vac |
Match the discharge current to your application risk level and installation position:
NSP Series | In | Imax | Iimp | Type | Best Application |
NSP20M | 20kA | 40kA | — | T2 | Light commercial sub-panels |
NSP30M | 30kA | 60kA | 3kA | T1+T2 | Building main switchboards |
NSP40S | 40kA | 80kA | — | T2 | Industrial sub-panels |
NSP60S | 60kA | 120kA | — | T2 | Heavy industrial main panels |
NSP80S | 80kA | 160kA | — | T2 | Critical infrastructure panels |
NSP25S | 25kA | — | 25kA | T1+T2 | Direct-lightning main entry |
NSP50S (Wind) | 50kA | 100kA | 50kA | T1+T2 | Wind turbine distribution |
Earthing System | Recommended Configuration | Typical Model Suffix |
TN-C (combined PEN) | 3-pole | TNCR |
TN-S (separate PE and N) | 4-pole or 3-pole + N | TNSR or TTR |
TT (separate earth) | 3-pole + N or 4-pole | TTR |
IT (isolated neutral) | 1-pole or 3-pole (L-PE) | IECR |
Single-phase with N | 1-pole + N (H2 series) | TTR |
The Up (clamping voltage) must be lower than the equipment impulse withstand voltage (Uimp):
Equipment Category | Uimp | NSP Series (Up) |
Cat. IV — Utility entrance | 6kV | Any NSP series |
Cat. III — Distribution boards | 4kV | Any NSP series |
Cat. II — Appliances, motors | 2.5kV | NSP40S–80S (Up ≤2.5kV) |
Cat. I — Sensitive electronics | 1.5kV | NSP20M (Up = 1.8kV) + 2-stage cascade |
• Selecting Uc too low — causes accelerated aging and false alarms under normal operating conditions.
• Using Type 2 only at the main panel — inadequate if a lightning protection system (LPS) is installed.
• Ignoring the N-PE path — N-PE overvoltages during neutral-ground faults can damage sensitive equipment.
• Mismatching pole configuration to earthing system — leaves conductors unprotected.
• Forgetting signal line protection — power SPDs alone do not protect SCADA, Ethernet, or analog lines.
Selecting the right NSP Series SPD is a systematic process: classify by IEC protection type, confirm continuous operating voltage, choose a discharge current rating matching your lightning risk, match the pole configuration to your earthing system, and verify Up is low enough for your most sensitive loads. Eaton's NSP matrix — from 20kA to 160kA and from 260Vac to 1500Vdc — ensures there is a purpose-engineered device for every challenge.
Technical specifications sourced from Eaton NSP Series product catalog. Always verify with the official datasheet before finalizing your design.
New industry Technology regarding to Bussmann fuse, ABB breakers, Amphenol connectors, HPS transformers, etc.