New industry Technology regarding to Bussmann fuse, ABB breakers, Amphenol connectors, HPS transformers, etc.
A Battery Energy Storage System is not a single circuit. It is a cascade of voltage domains, power conversion stages, and fault potential zones. Bussmann's application engineering documentation identifies five distinct protection levels within a complete ESS installation -- each with different voltage, current, and time-constant requirements.
BESS Protection Zones and Bussmann Solutions
Zone | Voltage Range | Current Range | Bussmann Recommendation |
Battery Module/Pack | < 100 Vdc | < 250 A | EVH (70V) / BS88 (150V) |
Battery Rack | 600–1500 Vdc | N × kA | BS88 500V / FWH-C / 170M 800V / 170M 1000V |
DC Combiner Box | 600–1500 Vdc | N × kA | 170M17XX (800V) / 170M18XX (1000V) / CBX |
PCS DC Side | 600–1500 Vdc | N × kA | Same as rack-level protection |
PCS AC Side | 400–690 Vac | N × kA | RT16/NT (gG), up to 1250A |
The module-level protection sits closest to the cells. At voltages typically below 100 Vdc and currents rarely exceeding 250 A, the EVH series (70 Vdc) and BS88 150V family provide appropriate protection. Operating class is aR (full-range semiconductor protection), meaning these fuses clear both overloads and short circuits. EVH fuses are particularly well-suited here: compact dimensions fit within tight battery module housings, and their low I2t characteristic limits energy let-through, protecting lithium-ion cells from arc damage during string-level faults.
As battery modules are series-stacked into racks, voltage escalates dramatically. A 1500 Vdc rack requires dedicated high-voltage protection. At this level, Bussmann recommends: BS88 FE/EET/FEE for 500 Vdc rack segments; FWH-C series for 500 Vdc up to 800A; 170M17XX for 800 Vdc racks; 170M18XX for 1000 Vdc racks; and CBX01S for 1000 Vdc compact applications. The interrupting rating requirement is determined by the number of parallel battery strings -- a system with 10 parallel strings can deliver fault currents well exceeding 50 kA, making high-IR fuses (50 kA minimum) mandatory.
The combiner box aggregates multiple rack outputs into a single DC bus feeding the PCS. Fuse selection mirrors rack-level protection but adds coordination requirements: the combiner fuse must trip before upstream converter fuses only for faults within the combiner itself. This selective coordination requires careful I2t matching across protection zones -- the combiner fuse must have lower total clearing I2t than the upstream main bus fuse at the same fault current.
The Power Conversion System is a bidirectional DC/AC converter. Its DC side sees the full system voltage and current. For a 500 kW PCS at 1000 Vdc, the DC side current is approximately 500A -- requiring a 500A or 630A 170M18XX fuse. For a 2 MW PCS at 1000 Vdc, the 2,000A level exceeds single fuse ratings. In this case, the PCS manufacturer typically provides internal protection at the module level, with each 500 kW module fused independently.
The AC side of the PCS connects to the grid or local load. RT16/NT fuses provide gG general-purpose protection with ratings from 4A to 1250A at AC 500V. For selective coordination with downstream AC breakers, RT16 with class gTr (time-delay) characteristics is recommended for transformer-fed circuits where inrush currents could cause nuisance trips with standard gG fuses.
The energy storage industry is moving toward 1500 Vdc bus architectures to reduce conductor costs. Bussmann's standard catalog tops out at 1000 Vdc for the 170M and CBX families. For 1500 Vdc applications, three approaches are used: two fuses in series (each fuse sees 750V, both rated for full fault current); splitting 1500 Vdc systems into two 750 Vdc buses each protected by 1000 Vdc fuses; or custom Bussmann solutions developed for large-scale BESS projects. Contact Bussmann engineering for 1500 Vdc application support.
New industry Technology regarding to Bussmann fuse, ABB breakers, Amphenol connectors, HPS transformers, etc.