New industry Technology regarding to Bussmann fuse, ABB breakers, Amphenol connectors, HPS transformers, etc.
Short-circuit thermal stability is a concept every electrical engineer should know well. When a fault current flows through a conductor, it generates heat. Thermal stability measures the ability of conductors and circuit elements to withstand the enormous heat produced during a very brief short-circuit event. Per code, the circuit must be interrupted before the conductor reaches its maximum allowable temperature.

Fig.1 — Substation distribution panel installation
The following example is based on an actual residential building electrical design. The project has an underground substation with two 800 kVA transformers. A self-use distribution panel (for fans, lighting, and maintenance outlets) is installed inside the substation: capacity 10 kW, calculated load current 16 A, incoming cable NH-YJV-1kV 5×16, 5 m long, connected directly to the low-voltage transformer bus.
S = 800 kVA
RT = 1.90 mΩ
XT = 13.27 mΩ
Busbar: TMY-3(100×8)+(80×8), L₁ = 6 m
R₁ = 0.04 × 6 = 0.24 mΩ
X₁ = 0.182 × 5 = 1.092 mΩ
Cable: NH-YJV-1kV 5×16, L₂ = 5 m
R₂ = 1.097 × 5 = 5.485 mΩ
X₂ = 0.087 × 5 = 0.435 mΩ
RK1 = RT + R1 + R2 = 1.90 + 0.24 + 5.485 = 7.625 mΩ
XK1 = XT + X1 + X2 = 13.27 + 1.092 + 0.435 = 14.797 mΩ
ZK1 = sqrt(R² + X²) = 16.65 mΩ
IK1 = 1.05 × 380 / (√3 × 16.65) = 13.84 kA
Fig.2 — Short-circuit impedance calculation diagram
Per GB 50054-2011 (Low-Voltage Electrical Installations Design Code), Clause 3.2.14, the conductor cross-section must satisfy:
S ≥ I × √t / k
Symbol | Meaning | Value |
S | Conductor cross-section (mm²) | — |
I | RMS short-circuit current (A) | 13,840 A |
t | Protective device operating time (s) | 0.02 s (20 ms instantaneous trip) |
k | Material constant (copper, GB50054 Annex A) | 143 |
S ≥ 13840 × √0.02 / 143 = 13.7 mm²
Minimum required cross-section: 13.7 mm². The original design specifies NH-YJV-1kV 5×16 (16 mm²) — larger than 13.7 mm², so it passes thermal stability verification.
Key takeaway: Although the self-use panel only draws 16 A in normal operation (meaning a 6 mm² cable would suffice by load current alone), the panel's proximity to the transformer forces a cable upgrade to 16 mm² to satisfy thermal stability. If you're close to the source, always run the thermal stability check.
In civil building electrical design, the closer the load is to the substation (and thus to the transformer), the lower the circuit impedance — and the higher the prospective short-circuit current. Incoming cable selection must account for both normal load current and short-circuit thermal stability.
· Always perform a thermal stability check for distribution panels located inside or immediately adjacent to a substation.
· Panels far from the transformer will naturally have higher impedance, which reduces the fault current.
· The instantaneous trip time of the upstream MCCB (typically 20 ms) is used as the fault clearing time t.
· The material constant k = 143 applies to copper conductors with XLPE insulation; consult GB50054 Annex A for other types.

New industry Technology regarding to Bussmann fuse, ABB breakers, Amphenol connectors, HPS transformers, etc.