Eaton MCCB,eaton circuit breaker catalog pdf, Molded Case Circuit Breaker,eaton mccb catalogue, eaton nzm mccb catalogue pdf
The NZM11-500/ZM11-250-3200-CNA is a Klockner-Moeller molded case circuit breaker for three-pole (3P) applications with a 250A current rating. Its adjustable thermal trip spans 160-250A, setting overload protection within the available current range, while the adjustable instantaneous trip covers 1600-3200A for magnetic fault response. Rated for 480 Y / 277 V, the breaker has a 690V rated insulation voltage. Switching capacity is 50kA@240V, 35kA@480v, and 25kA@600V, giving installation planners defined fault-current values for system matching. Line and load cable connections support panel wiring. IEC certification indicates compliance with the specified breaker standard, and frame size 11 supports frame matching with compatible equipment.
| Electrical rating | |
| Amperage Rating | 250A |
| Trip Type | adj thermal trip |
| Physical details | |
| Poles | 3P |
| General information | |
| Standards | IEC |