Bussmann 12TDLEJ63 transformer protection fuse

Bussmann 12TDLEJ63 transformer protection fuse

Manufacturer:Bussmann

Description :Bussmann 12TDLEJ63 current limiting fuse for transformer protection 12KV, 63amp

Stock quantity(PCS) :3

Lead time ( Weeks ) :

Categories:current limiting fuse; medium voltage fuse; time-delay fuse; ferrule fuse; transformer protection fuse;

Browse:

  • Specification
  • Datasheet download

Bussmann 12TDLEJ63 DIN Dimensioned IEC Fuse,ABPower_A bussmann fuse world.    


Fuse Application:

Transformer Protection

fuse rating:

12KV,63amp; 

fuse type:

DIN medium voltage fuse. 

Fuse cross reference: 

Cooper Xian fusegear, SDLDJ-12kV/63A.

Fuse size:

Busmsann transformer fuse.png

Current limiting fuse Caution

 

To ensure proper application of Bussmann current limiting fuse, it’s important that following additional rules be applied.

1, Current limiting fuse produce arc voltages that exceed the system voltage.

 Care must be taken to make sure that the peak voltage does not exceed the insulation level of the system. If the fuse voltage rating is not permitted to exceed 140% of the system voltage, there should not be a problem. This does not mean that a higher rated fuse cannot be used, but points out that one must be assured that the system insulation level (BIL) will handle the peak arc voltage produced.

2, As with the expulsion fuse, Bussmann current-limiting fuses must be properly coordinated with other protective devices on the system. For this to happen the rules for applying an expulsion fuse must be used at all currents that cause the fuse to interrupt in 0.01 seconds or greater.

When other current-limiting protective devices are on the system it becomes necessary to use I2t values for coordination at currents causing the fuse to interrupt in less than 0.01 seconds. These values may be supplied as minimum and maximum values or minimum melting and total clearing I2t curves. In either case, the following rules should be followed.

1, The minimum melting I2t of the fuse should be greater than the total clearing I2t of the downstream current-limiting device.

2, The total clearing I2t of the fuse should be less than the minimum melting I2t of the upstream current- limiting device.

 

IF you need more Bussmann fuses parameter,

Pls contact: ab@ bussmannpower.com

Skype: 18802904194

ABPower website:www.bussmannpower.com


690VAC current limiting fuse: 100FE, 170M1322 etc;

1000VAC semiconductor fuse: 170M2682,170M3958 etc;

1000VDC PV fuse:PV-125ANH1, PV-15A10F etc;

1250VAC high speed fuse: 170M6339, 170M5138 etc;

1500VAC semiconductor fuse: 170M2083, 1500amp 1500VDC fuse; 170M6734,800amp 1500VAC fuse.

12~24KV transformer protection current limiting fuse: 12TDLEJ63, 24TDLEJ 63;

Motor ciuicuit protection fuse: 7.2CAV10;


TAG:   bussmann medium voltage fuse; current limiting fuse;

Tell us what you need

Latest News

Latest News

MORE

Recommended News

Recommended News

MORE